PowerLogic™ PM5500 series user manual

Chapter 8—Input / Output

 

 

6.Configure the other setup parameters as required.

7.Click Send to save your changes.

Digital input setup parameters available through ION Setup

Parameter

Values

Description

 

 

 

Label

Use this field to change the default label and assign a

descriptive name to this digital input.

 

 

 

 

This field displays how the digital input functions.

 

 

• Normal: the digital input is either associated with a

 

 

digital input alarm, or it is not associated with

 

 

another meter function. The meter counts and

 

 

records the number of incoming pulses normally.

 

 

• Demand Sync: the digital input is associated with

 

 

one of the input sync demand functions. The meter

Control Mode

Normal, Demand Sync, Input

uses the incoming pulse to synchronize its demand

Metering, Multi-Tariff

period with the external source.

 

 

• Input Metering: the digital input is associated with

 

 

one of the input metering channels. The meter

 

 

counts and records the number of incoming pulses

 

 

and related consumption data associated with the

 

 

pulses.

 

 

Multi-Tariff: the digital input is associated with the

 

 

multi-tariff function. See “Input mode overview” on

 

 

page 105.

 

 

Debounce is the time delay that compensates for

 

 

mechanical contact bounce. Use this field to set how

Debounce

0 to 1000

long (in milliseconds) the external signal must remain in

a certain state to be considered a valid state change.

 

 

 

 

Allowable values are increments of 10 (i.e., 10, 20, 30,

 

 

etc., up to 1000 ms).

Associations

This field displays additional information if the digital

input is already associated with another meter function.

 

 

Configuring digital inputs using the front panel

You can use the front panel to configure the digital inputs.

Digital input setup menu tree

Maint

Reset

 

 

 

 

 

 

Setup

Meter

 

 

 

 

 

 

Comm

 

 

 

 

 

 

Alarm

 

 

 

 

 

 

I/O

LED

D In

D Out

Inp Mtr

1.Navigate to Maint > Setup.

2.Enter the setup password (default is “0”), then press OK.

3.Navigate to I/O > D In.

4.Move the cursor to point to the digital input you want to set up, then press Edit.

5.Move the cursor to point to the parameter you want to modify, then press Edit.

NOTE: If Edit is not displayed, it means the parameter is either read-only or can only be modified through software.

6.Modify the parameter as required, then press OK.

HRB1684301-01