Chapter 9—Meter resets

PowerLogic™ PM5500 series user manual

 

 

Single resets

Single resets allow you to clear data only in a specific register or register type.

1.Navigate to Maint > Reset.

2.Move the cursor to point to Single Reset, then press Select.

3.Move the cursor to point to the parameter you want to reset, then press Reset. If there are additional options for the parameter, press Select, move the cursor to point to the option you want, then press Reset.

Single reset options

Parameter

 

Option

Description

 

 

 

 

Energy

Accumulated

 

Clears all accumulated energy values (kWh,

 

kVARh, kVAh).

 

 

 

 

 

 

Select which demand registers to clear

Demand

Power, Current, Input Metering

(power demand, current demand or input

 

 

 

metering demand).

 

Event Queue

 

Clears the alarm event queue register (actve

 

 

alarms list).

 

 

 

Alarms

History Log

 

Clears the alarm history log.

 

 

 

 

All Alarm Counts,

Select “Counters”, then select which counter

 

 

 

Counters

(various alarm

to clear (choose all or individual alarm

 

counters) — see the

counters listed in the “Alarm counter options”

 

 

 

 

next table

table below).

 

 

 

 

 

 

All Dig In Timers,

 

 

Timers

Digital Input DI1,

Select “Timers”, then select which digital

 

Digital Input DI2,

input timer to clear (choose all or individual

 

 

Digital Input DI3,

digital input timers).

Digital Inputs

 

Digital Input DI4

 

 

All Dig In Counters,

 

 

 

 

 

Counters

Digital Input DI1,

Select “Timers”, then select which digital

 

Digital Input DI2,

input counter to clear (choose all or individual

 

 

Digital Input DI3,

digital input counters).

 

 

Digital Input DI4

 

 

 

All Dig Out Timers,

Select “Timers”, then select which digital

 

Timers

Digital Output DO1,

output timer to clear (choose all or individual

Digital Outputs

 

Digital Output DO2

digital output timers).

 

All Dig Out Counters,

Select “Timers”, then select which digital

 

 

 

Counters

Digital Output DO1,

output counter to clear (choose all or

 

 

Digital Output DO2

individual digital output counters).

Active Load Timer

 

 

Clears and restarts the load operation timer.

 

 

 

 

Multi-Tariff

 

 

Clears accumulated values in all tariff

 

 

register.

 

 

 

 

Reset All InptMtr, Reset InpMtr

Select which input metering channel (InpMtr

Input Metering

Chan 1, Reset InpMtr Chan 2, Reset

Chan) to clear (choose all or individual input

 

InpMtr Chan 3,Reset InpMtr Chan 4

metering channels).

4.Enter the reset password (default is “0”), then press OK.

5.Press Yes to confirm the reset or No to cancel and return to the previous screen.

Alarm counter options

Alarm counter

Option

Description

 

 

 

 

Over Current, Ph

 

 

 

 

Current

Under Current, Ph

Select which alarm counter register to reset from

Over Current, N

the current alarm condition counters.

 

 

 

 

 

Over Current, Gnd

 

 

 

 

 

Over Voltage, L-L

 

 

 

 

 

Under Voltage, L-L

 

 

 

 

 

Over Voltage, L-N

Select which alarm counter register to reset from

 

 

Voltage

Under Voltage, L-N

the voltage alarm condition counters.

 

 

 

Over Voltage Unbal

 

 

 

 

 

Over Voltage THD

 

 

 

 

 

Phase Loss

 

 

 

 

84

HRB1684301-01

Page 84