Chapter 10—Alarms

 

 

Alarm setup using the meter display

If your meter is equipped with a display:

1.Navigate to the alarms setup menu screens and select the alarm you want to set up. See “Front panel display and meter setup” on page 33 for basic instructions on using the front panel buttons to navigate the meter screens.

Maint

Reset

Setup

Meter

Comm

Alarm

1-Sec

Unary

Dig

Logic

Cust1s

2.Configure the setup parameters as explained in the different alarm setup sections.

3.When prompted, click Yes to save the changes to the meter.

NOTE: You must use ION Setup to create logic and custom (Cust1s) alarms. After the alarm is created, you can use ION Setup or the meter display to modify the alarm parameters.

NOTE: If you used ION Setup to program decimal values on a standard (1-Sec) alarm, do not use the meter display to make subsequent changes to any alarm parameters (inculding enable/disable), as doing so will cause removal of all decimals previously programmed through ION Setup.

Alarm setup using ION Setup

To set up all alarm types using ION Setup, open the Alarming setup screen to view the different alarm types. See the ION Setup online help for details.

Setting up unary alarms

Select the unary alarm you want to configure then use the following controls to set up the alarm (ION Setup controls are shown in parentheses).

Unary alarm setup parameters

Setting

Option or range

Description

 

 

 

Enable

Yes (checked) or No

This enables or disables the alarm.

(cleared)

 

 

Priority

High, Medium, Low, None

This sets the alarm priority and notification options.

See “Alarm priorities” on page 94.

 

 

Select Dig Output

None,

 

Digital Output D1,

Select the digital output(s) you want to control when the

(Outputs)

Digital Output D2,

alarm is triggered.

 

Digital Output D1 & D2

 

Setting up digital alarms

Select the digital alarm you want to configure then use the following controls to set up the alarm (ION Setup controls are shown in parentheses).

Digital alarm setup parameters

Setting

Option or range

Description

 

 

 

Enable

Yes (checked) or No

This enables or disables the alarm.

(cleared)

 

 

Priority

High, Medium, Low, None

This sets the alarm priority and notification options.

See “Alarm priorities” on page 94.

 

 