PowerLogic™ PM5500 series user manualChapter 14—Maintenance and upgrades

Meter firmware and upgrade method (Continued)

Firmware type

Upgrade method

Description

 

 

 

 

 

The FPGA app (field programmable gate array application)

FPGA app

DLF3000

firmware provides seamless transition between the meter’s

 

 

physical hardware and the firmware code.

 

 

The Ethernet files control how the meter webpages are

Ethernet

FTP

displayed. The files in the FW folder contains the code and

initialization files to run Ethernet communications. The www

 

 

 

 

folder contains the webpages and javascript files.

 

 

 

Using DLF300 to upgrade firmware

1.Download the latest version of DLF3000 from www.schneider-electric.com, then install it on your computer.

NOTE: DLF3000 is a free Schneider Electric utility for downloading firmware to your meter.

2.Download your meter’s firmware from www.schneider-electric.com.

3.Start DLF3000.

4.Click Add. Navigate to the folder where you saved your meter’s firmware.

5.Select the firmware file and click Open.

6.Select the firmware, then click Next.

7.If you haven’t defined an upgrade system yet:

Click New, then type in the box to assign a system name

Click Add, then type in the box to assign a communications connection name

Select the communications driver (Modbus/TCP Driver or Serial Driver)

8.Click Continue.

9.If you are using Modbus over TCP to upgrade, type the meter’s IP address in the box, then click OK.

10.Click Add Device.

Type in the box to assign a device name

Select the device type from the list

Select the connection name, i.e., the one you defined in the previous step.

11.Click Next.

12.Make sure the connection name, i.e., the one you defined in the previous step, is still selected. Enter the device address.

13.Select the protocol (e.g., Modbus).

14.Click OK.

15.Click Next.

16.Select the device name from the Download Candidate Devices pane, then click the right arrow button to move the selection to the Download Target Devices pane.

17.Select the meter firmware in the Firmware to field.

18.Click Next.

19.Click Health Check to confirm the meter is communicating. The Health Status shows Passed to indicate successful communications.

20.Click Next.

HRB1684301-01

123

Page 123
Image 123
Schneider Electric HRB1684301-01 user manual Using DLF300 to upgrade firmware, Click Continue, Click Add Device, Ftp