PowerLogic™ PM5500 series user manualChapter 8—Input / Output

Alarm / energy pulsing LED setup parameters

 

Setting

 

 

Option or range

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disabled turns off the LED completely.

 

Mode

 

 

Disabled, Alarm, Energy

Alarm sets the LED for alarm notification.

 

 

 

 

 

 

 

Energy sets the LED for energy pulsing.

 

 

 

 

 

 

Active Del,

 

 

 

 

 

 

 

Active Rec,

 

 

 

 

 

 

 

Active Del + Rec,

 

 

Parameter

 

 

Reactive Del,

Select which accumulated energy channel to monitor and

 

 

 

Reactive Rec,

use for energy pulsing. This setting is ignored when the

 

 

 

 

 

 

Reactive Del + Rec,

LED mode is set to Alarm.

 

 

 

 

 

 

Apparent Del,

 

 

 

 

 

 

 

Apparent Rec,

 

 

 

 

 

 

 

Apparent Del + Rec

 

 

 

 

 

 

 

 

When configured for energy pulsing, this setting defines

 

Pulse Wt. (p/k_h)

1 to 9999999

how many pulses are sent to the LED for every 1 kWh,

 

1 kVARh or 1kVAh accumulated energy. This setting is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ignored when the LED mode is set to Alarm.

 

 

 

 

 

 

 

 

5. Press

 

or

 

to modify the parameter as required, then press OK.

 

 

6. Press to exit. Press Yes to save your changes.

Configuring the LED or digital output for energy pulsing using

ION Setup

You can use the ION Setup to configure your meter’s LED or digital output for energy pulsing.

1.Start ION Setup.

2.Connect to your meter

3.Navigate to I/O configuration > Energy Pulsing.

4.Select the LED or a digital output to configure and click Edit. The setup screen is displayed.

5.Enter a descriptive name for the digital output’s Label.

6.Configure the other setup parameters as required.

7.Click Send to save your changes.

Alarm / energy pulsing LED setup parameters available through ION Setup

Parameter

Values

Description

 

 

 

 

 

Off disables the LED.

Mode

Off, Alarm, Energy

Alarm sets the LED for alarm notification.

 

 

Energy sets the LED for energy pulsing.

 

 

When configured for energy pulsing, this

Pulse Wt. (p/k_h)

1 to 9999999

defines how many pulses are sent to the LED

for every 1 kWh, 1 kVARh or 1kVAh of

 

 

 

 

accumulated energy.

 

 

 

 

Active Energy Delivered,

 

 

Active Energy Received,

 

 

Active Energy Del+Rec,

 

Channel

Reactive Energy Delivered,

Select which accumulated energy channel to

Reactive Energy Received,

monitor and use for energy pulsing.

 

Reactive Energy Del+Rec,

 

 

 

Apparent Energy Delivered,

 

 

Apparent Energy Received

 

 

Apparent Energy Del+Rec

 

Related topics

See “Alarm display and notification” on page 102 for details on using the front panel to view and acknowledge alarms.

See “Alarm priorities” on page 96 for a detailed description on the alarm / energy pulsing LED’s behavior when it is configured for alarm notification.

HRB1684301-01