Chapter 2—Hardware reference

PowerLogic™ PM5500 series user manual

 

 

LED indicators

The LED indicators alert or inform you of meter activity.

Location of LEDs

 

 

 

PM5560 / PM5561

PM5563

A

Alarm / energy pulsing LED

 

 

B

Heartbeat / serial

 

 

communications LED

All meter models

 

C

Ethernet communications LEDs

C

 

 

 

Alarm / energy pulsing LED

The alarm / energy pulsing LED can be configured for alarm notification or energy pulsing.

NOTE: The alarm / energy pulsing LED on the PM5561 is permanently set for energy pulsing and cannot be disabled or used for alarms.

When configured for alarm notification, this LED flashes when a high, medium or low priority alarm is tripped. The LED provides a visual indication of an active alarm condition or an inactive but unacknowledged high priority alarm.

When configured for energy pulsing, this LED flashes at a rate proportional to the amount of energy consumed. This is typically used to verify the power meter’s accuracy.

Related topics

See “Energy pulsing” on page 80 for details on configuring the alarm / energy pulsing LED for energy pulsing.

See “LED alarm indicator” on page 99 for details on configuring the alarm / energy pulsing LED for alarming.

Heartbeat / serial communications LED

The heartbeat / serial communications LED blinks at a slow, steady rate to indicate the meter is operational. The LED flashes at a variable, faster rate when the meter is communicating over a Modbus serial communications port.