Chapter 8—Input / Output

PowerLogic™ PM5500 series user manual

 

 

Input metering setup menu tree

Maint

Reset

 

 

 

 

 

 

Setup

Meter

 

 

 

 

 

 

Comm

 

 

 

 

 

 

Alarm

 

 

 

 

 

 

I/O

LED

D In

D Out

Inp Mtr

1.Navigate to Maint > Setup.

2.Enter the setup password (default is “0”), then press OK.

3.Navigate to I/O > Inp Mtr.

4.Move the cursor to point to the input metering channel you want to set up, then press Edit.

5.Move the cursor to point to the parameter you want to modify, then press Edit.

NOTE: If Edit is not displayed, it means the parameter is either read-only or can only be modified through software.

6.Modify the parameter as required, then press OK.

7.Move the cursor to point to the next parameter you want to modify, press Edit, make your changes, then press OK.

8.Press to exit. Press Yes to save your changes.

Input metering setup parameters

Parameter

Values

Description

 

 

 

 

 

This can be modified only through software. Use this

Label

field to assign names to the input metering channels

 

 

(Channel 1 to 4).

Pulse Weight

0 to 99.99999

Use this to specify the quantity or value each pulse

represents.

 

 

 

None, Wh, kWh, MWh,

 

Unit Code

VARh, kVARh, MVARh,

Select the unit of measurement associated with the

VAh, kVAh, MVAh, gal, BTU,

 

L, m3, MCF, lbs, kg, klbs,

monitored value.

 

Therm

 

 

(see table in “Demand

For time-based values (such as kWh), this provides the

 

associated demand units (kW) for demand calculations.

Demand Code

measurements for input

For other values (such as kg), this can be configured to

 

metering” on page 74)

 

provide rate information (kg/h).

 

 

 

 

 

 

 

Set Mode to Pulse to count only complete pulses. Set

Mode

Pulse or Transition

Mode to Transition to count each ON-to-OFF or OFF-to-

 

 

ON status change.

Digital Inputs

Digital Input DI1 to DI4

Select the digital input port that is used for input

metering.

 

 

Demand measurements for input metering

Based on the unit code selected, the following demand codes are set or selectable.

Input metering unit and demand measurements

Unit Code

Demand Code

Description

 

 

 

None

None

Default setting for the input metering channels.

 

 

 

Wh

 

Watt-hour kiloWatt-hour and MegaWatt-hour

 

 

kWh

kW

measurements are converted to calculate demand in

 

 

kW.

MWh

 

 

 

 

 

 

VARh

 

VAR-hour kiloVAR-hour and MegaVAR-hour

 

 

kVARh

kVAR

measurements are converted to calculate demand in

 

 

kVAR.

MVARh

 

 

 

 

 

 

74