Chapter 4—Remote meter setup

PowerLogic™ PM5500 series user manual

 

 

4.Log in to the meter webpages. The default login values are:

Username = user1

Password = pass1

5.Click Setup > Ethernet.

6.Modify the Ethernet setup parameters with the settings your system administrator assigned for the meter.

Ethernet & TCP/IP

 

Parameter

Description

 

 

 

 

Ethernet

 

MAC Address

Displays the meter’s factory-programmed MAC address.

 

This information is read-only and cannot be changed.

 

 

 

 

 

 

This controls the network protocol for your device (which the

 

 

 

meter uses to obtain its IP address):

 

 

 

• DHCP: Dynamic Host Configuration Protocol

 

 

 

• BOOTp: Bootstrap Protocol

 

 

IP Address Acquistion

• Static: Use the static value programmed in the

 

 

IP Address setup register

 

 

Mode

• Default: Use 85.16 as the first two values of the

IP Parameters

 

 

IP address, then convert the last two hexadecimal

 

 

values of the MAC address to decimal and use this as

 

 

 

 

 

 

the last two values of the IP address.

 

 

 

Example: MAC address = 00:80:67:82:B8:C8

 

 

 

Default IP address = 85.16.184.200

 

 

IP Address

The internet protocol address of your device.

 

 

 

 

 

 

Subnet Mask

The Ethernet IP subnetwork address of your network.

 

 

 

 

 

 

Default Gateway

The Ethernet IP gatway address of your network.

 

 

 

 

7.Click Apply to send and save the new settings to the meter.

8.Click Logout to exit the meter’s webpages.

Meter setup through Ethernet

After the meter’s Ethernet port is configured and connected to the LAN, you can:

Use a web browser to connect to the meter webpages and configure Ethernet settings, webpage users and data log export schedules.

Use ION Setup to configure all other meter setup parameters.

Related topics

See “Setting up Ethernet communications” on page 40 for details on using the meter’s display panel to configure the Ethernet port.

RS-485 port setup

Use ION Setup to modify the meter’s default RS-485 settings before connecting the meter to the RS-485 bus. The meter is factory-configured with the following default serial communications settings:

Protocol = Modbus RTU

Address = 1

Baud rate = 19200

Parity = Even

You can use a communications converter (USB to RS-485 or RS-232 to RS-485) or

Ethernet gateway device to connect to the meter.