Schneider Electric HRB1684301-01 user manual Current, Voltage, Harmonics

Models: HRB1684301-01

1 148
Download 148 pages 57.73 Kb
Page 62
Image 62

Chapter 7—Viewing meter data

PowerLogic™ PM5500 series user manual

 

 

Current

Amps

(I)

Voltage

Volts (U-V)

Phase

Dmd

Ig

V L-L (U) V L-N (V)

Iavg

Ia

Ib

Ic

In

Ig

 

 

 

 

 

 

Amps [I]

Phase

Instantaneous current measurements for each phase and neutral

(Ia [I1], Ib [I2], Ic [I3], In).

 

 

 

 

 

 

 

Dmd

Summary of peak current demand values at the last demand

interval for each phase and neutral (Ia [I1], Ib [I2], Ic [I3], In).

 

 

 

 

 

 

Real-time demand (Pres), peak demand (Peak) and predicted

 

Iavg, Ia [I1], Ib [I2], Ic [I3], In, Ig

demand (Pred) for the present interval. Average demand for the

 

 

 

previous (Last) interval.

 

 

Pk DT

Date and timestamp for the peak demand readings.

 

 

 

Ig

Average (Iavg), neutral (In) and residual/ground (Ig) current

 

 

 

 

Related topics

See “Current demand” on page 117.

Volts [U-V]

V L-L [U]

Line-to-line phase voltage (Vab [U12], Vbc [U23], Vca [U31]).

 

 

V L-N [V]

Line-to-neutral phase voltage (Van [V1], Vbn [V2]), Vcn [V3]).

 

 

Harmonics

Harm

 

 

 

V L-L (U)

 

 

 

 

 

 

 

V L-N (V)

 

 

 

 

 

 

 

 

Amps (I)

 

 

 

 

 

 

 

 

TDD / K

 

 

 

 

 

 

 

 

Crest

 

 

 

 

Fund

3-11

 

13-21

23-31

 

 

 

 

 

 

 

 

 

 

 

 

 

Fund

3-11

 

13-21

23-31

 

 

 

 

 

 

 

 

 

 

 

 

 

Fund

3-11

 

13-21

23-31

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Amps (I)

 

V L-L (U)

V L-N (V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Harm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V L-L [U]

Line-to-line voltage harmonics data: Numeric magnitude and

 

 

 

 

 

 

 

 

 

 

 

angle for the fundamental harmonic, and graphical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fund, 3-11, 13-21, 23-31

representation of harmonics for the 3rd to 11th, 13th to 21st, and

 

 

 

 

 

 

 

23rd to 31st odd harmonics for each line-to-line phase voltage

 

 

 

 

 

 

 

 

 

 

 

(Vab [U12], Vbc [U23], Vca [U31]).

 

 

 

 

 

V L-N [V]

Line-to-neutral voltage harmonics data: Numeric magnitude and

 

 

 

 

 

 

 

 

 

 

 

angle for the fundamental harmonic, and graphical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fund, 3-11, 13-21, 23-31

representation of harmonics for the 3rd to 11th, 13th to 21st, and

 

 

 

 

 

 

 

23rd to 31st odd harmonics for each line-to-neutral phase voltage

 

 

 

 

 

 

 

 

 

 

 

(Van [V1], Vbn [V2]), Vcn [V3]).

 

 

 

 

 

Amps [I]

Current harmonics data: Numeric magnitude and angle for the

 

 

 

 

 

 

 

 

 

 

 

fundamental harmonics, and graphical representation of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fund, 3-11, 13-21, 23-31

harmonics for the 3rd to 11th, 13th to 21st, and 23rd to 31st odd

 

 

 

 

 

 

 

 

 

 

 

harmonics for each phase current (Ia [I1], Ib [I2], Ic [I3]).

 

 

 

 

 

TDD/K

Total demand distortion and K-factor data for each phase voltage

 

 

 

 

 

(K-F A [K-F 1], .K-F B [K-F 2], K-F C [K-F 3]).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Crest

Crest factor data for each phase current (Ia [I1], Ib [I2], Ic [I3]),

 

 

 

 

 

 

 

 

 

 

 

line-to-line phase voltage (Vab [U12], Vbc [U23], Vca [U31]), and

 

 

 

 

 

 

 

Amps [I], V L-L [U], V L-N [V]

 

 

 

 

 

 

 

line-to-neutral phase voltage (Van [V1], Vbn [V2]), Vcn [V3]).

 

 

 

 

 

 

 

 

 

 

 

 

Related topics

See “Power quality” on page 121.

62

HRB1684301-01

Page 62
Image 62
Schneider Electric HRB1684301-01 user manual Current, Voltage, Harmonics