PowerLogic™ PM5500 series user manualChapter 2—Hardware reference

Power system setup parameters

Power system description

Direct connect maximum

# of VTs

Symbol

 

 

(if required)

Meter setting

UL

IEC

 

Single-phase 2-wire line-to-neutral

 

 

 

480 V L-N

480 V L-N

1 VT

1PH2W LN

 

 

 

Single-phase 2-wire line-to-line

 

 

 

600 V L-L

600 V L-L

1VT

1PH2W LL

 

 

 

Single-phase 3-wire line-to-line with

 

 

 

neutral

347 V L-N /

400 V L-N /

2VT

600 V L-L

690 V L-L

 

1PH3W LL with N

 

 

 

3-phase 3-wire Delta ungrounded

 

 

 

600 V L-L

600 V L-L

2 VT

3PH3W Dlt Ungnd

 

 

 

3-phase 3-wire Delta corner

 

 

 

grounded

600 V L-L

600 V L-L

2 VT

 

 

 

3PH3W Dlt Crnr Gnd

 

 

 

3-phase 3-wire Wye ungrounded

 

 

 

600 V L-L

600 V L-L

2 VT

3PH3W Wye Ungnd

 

 

 

3-phase 3-wire Wye grounded

 

 

 

600 V L-L

600 V L-L

2 VT

3PH3W Wye Gnd

 

 

 

3-phase 3-wire Wye resistance-

 

 

 

grounded

600 V L-L

600 V L-L

2 VT

 

 

 

3PH3W Wye Res Gnd

 

 

 

3-phase 4-wire open Delta center-

240 V L-N /

240 V L-N /

 

tapped

 

415 V L-N /

415 V L-N /

3 VT

480 V L-L

480 V L-L

 

3PH4W Opn Dlt Ctr Tp

 

N

 

 

 

 

 

3-phase 4-wire Delta center-tapped

240 V L-N /

240 V L-N /

 

 

415 V L-N /

415 V L-N /

3 VT

3PH4W Dlt Ctr Tp

480 V L-L

480 V L-L

 

 

 

 

 

N

 

 