Schneider Electric HRB1684301-01 user manual Digital inputs, Digital output connections

Models: HRB1684301-01

1 148
Download 148 pages 57.73 Kb
Page 26
Image 26

Chapter 2—Hardware reference

PowerLogic™ PM5500 series user manual

 

 

Digital output connections

 

 

D1

D2

D1

D2

 

+ -

+

-

 

 

 

LOAD

 

LOAD

 

 

≤ 125 mA

 

 

+

 

 

 

-

 

 

 

< 30 V AC

 

 

 

< 60 V DC

 

 

 

Related topics

See “Digital output applications” on page 77 for digital output use and configuration details.

Digital inputs

The meter is equipped with four digital input ports (S1 to S4). You can configure the digital inputs for use in status monitoring or input metering applications.

The meter’s digital inputs require an external voltage source to detect the digital input’s on/off state. The meter detects an on state if the external voltage appearing at the digital input is within its operating range.

The digital inputs require a 18 - 30 V AC or 12 - 30 V DC external voltage source to detect the digital input’s on/off state.

Digital input connections

S1

S2

 

S3

S4

+

-

+

-

+

-

+

-

+

 

 

 

 

 

 

 

18 - 30 V AC

 

 

 

 

 

 

 

12 - 60 V DC

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

+

 

 

 

 

 

 

 

18 - 30 V AC

 

 

 

 

 

 

 

12 - 60 V DC

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

+

-

+

18

- 30 V AC

 

 

12

- 60 V DC

-

 

 

18 - 30 V AC

12 - 60 V DC

Related topics

See “Digital input applications” on page 71 for digital input use and configuration details.