Schneider Electric HRB1684301-01 user manual Quadrant PF range PF register PF formula, Range

Models: HRB1684301-01

1 148
Download 148 pages 57.73 Kb
Page 140
Image 140

Chapter 16—Power, energy and power factor

PowerLogic™ PM5500 series user manual

 

 

PF value is calculated from the PF register value using the following formulas:

Quadrant

PF range

PF register

PF formula

range

 

 

 

 

 

 

 

Quadrant 1

0 to +1

0 to +1

PF value = PF register value

 

 

 

 

Quadrant 2

-1 to 0

-1 to 0

PF value = PF register value

 

 

 

 

Quadrant 3

0 to -1

-2 to -1

PF value = (-2) - (PF register value)

 

 

 

 

Quadrant 4

+1 to 0

+1 to +2

PF value = (+2) - (PF register value)

 

 

 

 

140

HRB1684301-01

Page 140
Image 140