See “Meter configuration using ION Setup” on page 53 to set up the meter using ION Setup.

Demand setup

Demand is a measure of average consumption over a fixed time interval.

Use the Demand setup screens to define power demand, current demand or input metering demand.

Demand setup menu tree

Maint

Reset

 

 

 

 

 

 

Setup

Meter

Basic

Adv

Dmd

Tariff

1.Navigate to Maint > Setup.

2.Enter the setup password (default is “0”), then press OK.

3.Navigate to Meter > Dmd.

4.Move the cursor to select Power Demand, Current Demand or Input Demand.

5.Move the cursor to point to the parameter you want to modify, then press Edit.

6.Modify the parameter as required, then press OK.

7.Move the cursor to point to the next parameter you want to modify, press Edit, make your changes, then press OK.

Power, current, or input demand setup parameters

Parameter

Values

Description

 

 

 

 

Timed Sliding Block

 

 

Timed Block

 

 

Timed Rolling Block

 

 

Input Sync Block

 

Method

Input Sync Roll Block

See “Power demand” on page 115 for

Cmd Sync Block

details.

 

 

Cmd Sync Roll Block

 

 

Clock Sync Block

 

 

Clock Sync Roll Block

 

 

Thermal

 

 

 

 

Interval

0 - 99

Set the demand interval, in minutes.

 

 

 

 

 

Applies only to rolling block methods.

Subinterval

0 - 99

Define how many subintervals the demand

 

 

interval should be equally divided into.

Select Dig Output

None, Digital Output D1, Digital

Select which digital output the end of

Output D2

demand interval pulse should be sent to.

 

 

None, Digital Input S1, Digital

Applies only to input sync methods.

Select Dig Input

Input S2, Digital Input S3, Digital

Select which digital input is used to sync

 

Input S4

the demand.

 

 

 

 

 

Applies only to clock sync methods (these

 

 

synchronize the demand interval to the

Clock Sync Time

0 - 2359

meter’s internal clock).

 

 

Define what time of day you want to

 

 

synchronize the demand

8. Press Yes to save your changes.