PowerLogic™ PM5500 series user manualChapter 3—Front panel display and meter setup

Ethernet port settings

Parameter

Values

Description

 

 

 

 

 

This controls the network protocol for your device

 

 

(what the meter uses to obtain its IP address).

 

 

• Stored: Use the static value programmed in the

 

 

IP Address setup register

 

 

• Default: Use 85.16 as the first two values of the

IP Method

Stored, Default, DHCP,

IP address, then convert the last two

BOOTP

hexadecimal values of the MAC address to

 

 

decimal and use this as the last two values of

 

 

the IP address.

 

 

Example: MAC address = 00:80:67:82:B8:C8

 

 

Default IP = 85.16.184.200

 

 

• DHCP: Dynamic Host Configuration Protocol

 

 

• BOOTP: Bootstrap Protocol

IP Address

Contact your local

The internet protocol address of your device.

 

 

 

The Ethernet IP subnetwork address of your

Subnet

network administrator

network (subnet mask).

 

for parameter values.

 

 

Gateway

 

The Ethernet IP gateway address of your network.

 

 

 

HTTP Server

Enabled, Disabled

Controls whether your device’s webserver and

webpages are active or not.

 

 

 

 

This is the meter’s device name and is factory set to

Device Name

(see description)

PM55#-xxx (where xxx is the serial number of the

meter). This can be used as a DNS entry that maps

 

 

the device name to the IP address assigned by the

 

 

DHCP server.

7. Press to exit. Press Yes to save your changes.

Related topics

See “Configuring Ethernet settings using a browser” on page 56 to set up the Ethernet port using the meter webpages.

Alarms setup

An alarm is the meter’s means of notifying you when an alarm condition is detected, such as an error or an event that falls outside of normal operating conditions.

Related topics

See “Alarms” on page 89 for a comprehensive description and detailed setup instructions.

Input / output setup

The meter’s input/output (I/O) ports extend the capabilities of the meter. The I/O ports can be configured using the front panel or ION Setup.

Related topics

See “Input / Output” on page 71 for a comprehensive description and setup instructions.

See “Specifications” on page 28 for electrical characteristics and limits of the meter’s I/O ports.

HRB1684301-01

41