Schneider Electric HRB1684301-01 Configuring tariffs, Configuring time of day mode tariffs

Models: HRB1684301-01

1 148
Download 148 pages 57.73 Kb
Page 106
Image 106

Chapter 11—Multi-tariff feature

PowerLogic™ PM5500 series user manual

 

 

Configuration 2: 8 tariff assignment using 4 digital inputs (Continued)

T5

0

1

0

1

 

 

 

 

 

T6

0

1

1

0

 

 

 

 

 

T7

0

1

1

1

 

 

 

 

 

T82

1

0

0

0

1This digital input configuration (0000) means there are no active tariffs (all tariffs are disabled)

2Any configuration above 8, i.e., 1001 and higher, is invalid and therefore ignored by the meter (the active tariff does not change).

Configuring tariffs

This section explains how to set up tariffs.

Tariff setup menu tree

Maint

Reset

 

 

 

 

 

 

Setup

Meter

Basic

Adv

Dmd

Tariff

You can change the tariff mode using the front panel.

When the meter is set to command mode for tariffs, the active tariff is controlled by Modbus commands sent from your energy management system or other Modbus master.

Related topics

Search your meter’s Modbus register list at www.schneider-electric.com to download the Modbus map.

Configuring time of day mode tariffs

When the meter is set to time of day for tariffs, the active tariff is determined by the day type, the start and end times, and the start and end dates. The time of day tariff is not a calendar; the meter does not calculate the corresponding day of the week to a specific date, but February 29th is considered a valid date if you are programming the meter during a leap year.

When you enter tariff times using the front panel, be aware that the displayed minute value includes the entire minute. For example, an end time of 01:15 includes the time from 01:15:00 through 01:15:59. To create a tariff period that starts right after this, you must set the next tariff’s start time to 01:16. Although it may appear that there is a gap between these tariffs, there is not.

NOTE: You must always set the tariff times to UTC (GMT, Greenwich Mean Time), not local time. The GMT Offset (h) setup parameter does not apply to tariff times.

Use ION Setup to configure time of day mode tariffs.

Related topics

See “Meter configuration using ION Setup” on page 51 to configure the tariffs and other parameters using ION Setup.

Configuring input mode tariffs using the front panel

When you set the tariff type to Input, the active tariff is determined by the status of the digital inputs.

106

HRB1684301-01

Page 106
Image 106
Schneider Electric HRB1684301-01 Configuring tariffs, Configuring time of day mode tariffs, Tariff setup menu tree