PowerLogic™ PM5500 series user manualChapter 3—Front panel display and meter setup

Basic setup parameters (Continued)

Parameter

Values

Description

 

 

 

Sys Frequency (Hz)

50, 60

Select the frequency of the electrical power

system, in Hz.

 

 

Phase Rotation

ABC, CBA

Select the phase rotation of the 3-phase system.

 

 

 

7. Press Yes to save your changes.

Related topics

See “Power system” on page 20 for descriptions and symbols of the different electrical power systems supported by the meter.

See “Meter configuration using ION Setup” on page 53 to set up the meter using ION Setup.

Configuring advanced setup parameters

The advanced setup screens let you configure the following:

Load timer setpoint: defines the active load current, which is the minimum input current required to start and keep the active load timer counting.

Peak current demand for total demand distortion: specifies the minimum current demand value required to include in total demand distortion calculations.

Advanced setup menu tree

Maint

Reset

 

 

 

 

 

 

Setup

Meter

Basic

Adv

Dmd

Tariff

1.Navigate to Maint > Setup.

2.Enter the setup password (default is “0”), then press OK.

3.Navigate to Meter > Advan.

4.Move the cursor to point to the parameter you want to modify, then press Edit.

5.Modify the parameter as required, then press OK.

6.Move the cursor to point to the next parameter you want to modify, press Edit, make your changes, then press OK.

Advanced setup parameters

Parameter

Values

Description

 

 

 

 

 

This label identifies the device, e.g., “Power

Label

Meter”. You cannot use the front panel to edit

this parameter. Use ION Setup to change the

 

 

 

 

device label.

 

 

 

 

 

Specifies the minimum average current at the

Load Timer Setpt (A)

0 - 9

load before the timer starts. The meter begins

counting the number of seconds the load timer

 

 

is on (i.e., whenever the readings are equal to

 

 

or above this average current threshold.

 

 

Specifies the minimum peak current demand

 

 

at the load for inclusion in total demand

 

 

distortion (TDD) calculations. If the load

Pk I dmd for TDD (A)

0 - 9

current is below the minimum peak current

demand threshold, the meter does not use the

 

 

readings to calculate TDD. Set this to “0”

 

 

(zero) if you want the power meter to use the

 

 

metered peak current demand for this

 

 

calculation.

7. Press Yes to save your changes.

HRB1684301-01

37

Page 37
Image 37
Schneider Electric HRB1684301-01 user manual Configuring advanced setup parameters, Advanced setup menu tree, Abc, Cba