Schneider Electric HRB1684301-01 Input metering setup, Configuring input metering using ION Setup

Models: HRB1684301-01

1 148
Download 148 pages 57.73 Kb
Page 73
Image 73

PowerLogic™ PM5500 series user manual

Chapter 8—Input / Output

 

 

If you want to configure for kWh pulsing, you must adjust the pulse weight calculation and unit code as follows:

Pulse Weight = pulses/kWh = 1/0.125 = 8

Unit Code = kWh

Input metering setup

Input metering can be configured using the front panel or software.

NOTE: It is recommended you use ION Setup to configure input metering, as setup parameters that require text entry can only be modified using ION Setup.

Configuring input metering using ION Setup

You can use ION Setup to configure the input metering channels.

1.Start ION Setup.

2.Connect to your meter

3.Navigate to I/O configuration > Input metering.

4.Select an input metering channel to configure and click Edit. The Channel Setup screen is displayed

5.Enter a descriptive name for the metering channel’s Label.

6.Configure the other input metering parameters as required.

7.Click Send to save your changes.

Input metering setup parameters

Parameter

Values

Description

 

 

 

Label

Use this field to change the default label and assign a

descriptive name to this input metering channel.

 

 

Pulse Weight

0 to 99.99999

Use this field to specify the quantity or value each pulse

represents.

 

 

 

No units, Wh, kWh, MWh,

 

Units

VARh, kVARh, MVARh,

Select the unit of measurement associated with the

VAh, kVAh, MVAh, gal, BTU,

 

L, m3, MCF, lbs, kg, klbs,

monitored value.

 

Therm

 

 

(see table in “Demand

For time-based values (such as kWh), this provides the

 

associated demand units (kW) for demand calculations.

Rate

measurements for input

For other values (such as kg), this can be configured to

 

metering” on page 74)

 

provide rate information (kg/h).

 

 

 

 

 

 

 

Set Mode to Pulse to count only complete pulses. Set

Mode

Pulse or Transition

Mode to Transition to count each ON-to-OFF or OFF-to-

 

 

ON status change.

Available Inputs /

 

Select the digital input from the Available Inputs box and

Digital Input DI1 to DI4

use the right arrow button to assign the input metering

Assigned Inputs

 

channel to that digital input.

 

 

 

 

 

Configuring input metering using the front panel

You can use the front panel to configure the input metering channels.

HRB1684301-01

73

Page 73