Chapter 9

Meter resets

Reset commands clear the meter’s onboard data logs and related registers. Meter resets are typically performed after you make changes to the meter’s basic setup parameters (such as power system, frequency, or PT/CT settings), to clear invalid or obsolete data in preparation for putting the meter into active service.

The meter reset commands are grouped into two categories: Global Resets and Single

Resets.

Related topics

For meter reset procedures using ION Setup, see “Meter configuration using ION Setup” on page 51.

Front panel meter reset screens

To access the meter reset screens, navigate to Maint > Reset.

Reset menu tree

Maint

Reset

Global resets

Global resets allow you to clear all data of a particular type, such as all energy values or all minimum/maximum values.

Meter Initialization is a special command that clears the meter’s recorded logged data, counters and timers. It is common practice to initialize the meter after its configuration is completed, before adding it to an energy management system.

1.Navigate to Maint > Reset.

2.Move the cursor to point to Global Reset, then press Select.

3.Move the cursor to point to the parameter you want to reset, then press Reset.

Global reset options

Parameter

Description

 

 

Meter Initialization

Clears all data listed in this table (energy, demand, min/max values,

counters, logs, timers, and input metering data).

 

Energies

Clears all accumulated energy values (kWh, kVARh, kVAh).

 

 

Demands

Clears all the demand registers.

 

 

Min/Max

Clears all the minimum and maximum registers.

 

 

Alarm Counts & Logs

Clears all the alarm counters and alarm logs.

 

 

I/O Counts & Timers

Clears all the I/O counters and resets all the timers.

 

 

Input Metering

Clears all input metering energy data.

 

 

4.Enter the reset password (default is “0”), then press OK.

5.Press Yes to confirm the reset or No to cancel and return to the previous screen.