Chapter 4—Remote meter setup

PowerLogic™ PM5500 series user manual

 

 

reconfigure ION Setup to match the new settings to re-establish communications with your meter.

1.If applicable, disconnect all serial devices presently connected to the Ethernet gateway’s RS-485 port.

2.Configure the Ethernet gateway’s serial port settings to match the meter’s default serial communications settings:

Baud rate = 19200

Parity = Even

3.Connect the meter’s RS-485 port to the Ethernet gateway.

4.Connect the Ethernet gateway to the LAN.

5.Start ION Setup in Network mode.

6.Add an Ethernet gateway site and set its properties:

IP address = IP address of the Ethernet gateway

Port = 502 (for Modbus RTU)

7.Add a meter to the site and set its properties:

Type = PowerLogic PM5000 series Power Meter

Unit ID = 1

8.Use the RS-485 Base Comm setup screen to modify the meter’s serial communications settings.

RS-485 port settings

Parameter

Values

Description

 

 

 

 

 

Select the communications format used to transmit

 

Modbus RTU, JBus,

data. The protocol must be the same for all devices in a

Protocol

communications loop.

 

ASCII 8, ASCII 7

ION Setup does not support ASCII 8, ASCII 7 or JBus

 

 

 

 

protocols.

 

 

 

 

 

Set the address for this device. The address must be

 

 

unique for each device in a communications loop. For

 

 

JBus protocol, set the device ID to 255.

Address

1 to 247

This value is used in both Ethernet and serial

 

 

communications; if you change this value, you need to

 

 

update your meter properties in ION Setup to re-

 

 

establish Ethernet communications.

 

 

Select the speed for data transmission. The baud rate

Baud Rate

9600, 19200, 38400

must be the same for all devices in a communications

 

 

loop.

 

 

Select None if the parity bit is not used. The parity

Parity

Even, Odd, None

setting must be the same for all devices in a

 

 

communications loop.

9.Click Send to save your changes to the meter. You need to reconfigure ION Setup to match the changed settings in order to re-establish communications with your meter.

NOTE: If you set the protocol to ASCII 7, ASCII 8 or JBus, you cannot use ION Setup to reconnect to the meter — ION Setup does not communicate using these protocols.

10. Exit ION Setup.

Meter setup through RS-485

After the meter’s RS-485 port is configured and connected to the RS-485 network, you can use ION Setup to configure all other meter setup parameters.

Related topics

See “Setting up serial communications” on page 39 for details on using the meter’s display panel to configure the RS-485 port.