PowerLogic™ PM5500 series user manual

Chapter 10—Alarms

 

 

Active alarms

When an alarm condition becomes true (alarm = ON), the alarm is displayed on the active alarms screen. The alarm details (for low, medium and high priority alarms) are also recorded in the alarm history log.

Viewing active alarm details

1.Navigate to Alarm > Active.

2.Select the alarm you want to view (the latest ones appear on top). Press Detail.

NOTE: For unacknowledged high priority alarms, the Ack option appears on this screen. Press Ack to acknowledge the alarm, or return to the previous screen if you do not want to acknowledge the alarm.

The alarm details show the date and time of the alarm event, the type of event (e.g., pickup or unary), which phase the alarm condition was detected on, and the value that caused the alarm condition.

NOTE: Alarm details are not available if the alarm priority is set to None.

Alarm history

The alarm history log keeps a record of active alarms and past alarms. When an active alarm condition becomes false (alarm = OFF), the event is recorded in the alarm history log and alarm notification (alarm icon, alarm LED) is turned off.

Viewing alarm history details

1.Navigate to Alarm > Hist.

2.Select the alarm you want to view (the latest ones appear on top). Press Detail.

NOTE: For unacknowledged high priority alarms, the Ack option appears on this screen. Press Ack to acknowledge the alarm, or return to the previous screen if you do not want to acknowledge the alarm.

The alarm details show the date and time of the alarm event, the type of event (e.g., dropout or unary), which phase the alarm condition was detected on, and the value that caused the alarm condition to turn ON or OFF.

NOTE: Alarm details are not available if the alarm priority is set to None.

Alarm counter

Every occurrence of each type of alarm is counted and recorded in the meter. To view the alarm counters:

1.Select Alarm > Count. The Alarms Counter screen displays.

2.Scroll through the list to view the number of alarm occurrences for each type of alarm.

Rollover value

The alarm counters roll over to zero after reaching the value 9999.

Acknowledging alarms

This applies to high priority alarms. You can use the meter display or software to acknowledge alarms.