Chapter 2—Hardware referencePowerLogic™ PM5500 series user manual

Electrical characteristics (Continued)

 

Voltage unbalance

2.0%

 

 

 

Power quality

Voltage harmonics

2.0%

 

 

accuracy, as per

Voltage THD

2.0%

IEC 61557-12

 

 

Current harmonics

2.0%

 

 

 

 

 

Current THD

2.0%

 

 

 

 

VT primary

1.0 MV AC max

 

 

 

 

 

20 to 400 V L-N / 20 to 690 V L-L (Wye) or 20 to 600 V L-L

 

Measured voltage

(Delta)

 

 

UL Listed up to 347 V L-N / 600 V L-L

Voltage inputs

Measurement category

CAT III (6 kV rated impulse voltage)

 

 

 

 

Overload

480 V L-N / 828 V L-L

 

 

 

 

Impedance

5 MΩ

 

 

 

 

Frequency

50 or 60 Hz ±10% (45 - 70 Hz)

 

 

 

 

CT primary

32767 A max

 

 

 

 

CT secondary

Nominal: 5A (Class 0.2S) or 1 A (Class 0.5S)

 

 

 

 

Starting current

5 mA

 

 

 

 

Measured current with

50 mA to 10 A

 

overrange and crest factor

Current inputs

 

20 A continuous

 

Withstand

50 A at 10 sec/hr

 

 

500 A at 1 sec/hr

 

 

 

 

Impedance

< 0.3 mΩ

 

 

 

 

Frequency

50 or 60 Hz ±10% (45 - 70 Hz)

 

 

 

 

Burden

< 0.024 VA at 10 A

 

 

 

 

Operating range

100 to 480 V AC ± 10%

 

 

 

 

Installation category

CAT III 600V class per IEC 61010-1 edition 3

 

 

 

AC control power

Burden

5.0 W / 16.0 VA / 15.2 VAR max at 480 V AC

 

 

Frequency

50 or 60 Hz ±10%

 

 

 

 

 

Ride-through time

35 ms typical at 120 V L-N and maximum burden

 

129 ms typical at 230 V L-N and maximum burden

 

 

 

 

 

 

Operating range

125 to 250 V DC ±20%

 

 

 

DC control power

Burden

3.1 W typical, 5.0 W maximum at 125 V DC

 

 

 

 

Ride-through time

50 ms typical at 125 V DC and maximum burden

 

 

 

 

Number / type

2 - Form A solid-state digital outputs

 

 

 

 

Load voltage

30 V AC / 60 V DC maximum

 

 

 

 

Load current

125 mA maximum

 

 

 

 

ON resistance

8 Ω

Digital outputs

 

 

Pulse frequency

25 Hz maximum

 

 

 

 

Meter constant

1 to 9,999,999 pulses per kWh

 

 

 

 

Pulse width

50% duty cycle (20 ms minimum ON time)

 

 

 

 

Leakage current

1 micro Amps

 

 

 

 

Isolation

2.5 kV RMS for 60 seconds

 

 

 

 

Type

Amber LED, optical

 

 

 

Active alarm / energy

Pulse frequency

2.5 kHz maximum

 

 

Pulse width

50% duty cycle (200 microseconds minimum ON time)

pulsing LED

 

 

 

Meter constant

1 to 9,999,999 pulses per kWh

 

 

 

 

Wavelength

590 to 635 nm

 

 

 

28