Image 136

Chapter 16—Power, energy and power factor

PowerLogic™ PM5500 series user manual

 

 

Energy delivered / energy received

The meter interprets energy delivered or received according to the direction of real power (P) flow.

Energy delivered means positive real power flow (+P) and energy received means negative real power flow (-P).

Quadrant

Real (P) power flow

Energy delivered or received

 

 

 

Quadrant 1

Positive (+)

Energy delivered

 

 

 

Quadrant 2

Negative (-)

Energy received

 

 

 

Quadrant 3

Negative (-)

Energy received

 

 

 

Quadrant 4

Positive (+)

Energy delivered

 

 

 

Power factor (PF)

Power factor (PF) is the ratio of real power (P) to apparent power (S), and is a number between 0 and 1.

P

PF = --

S

An ideal, purely resistive load has no reactive components, so its power factor is one (PF = 1, or unity power factor). A purely inductive or capacitive load no resistive components, so its power factor is zero (PF = 0).

True PF and displacement PF

The meter supports true power factor and displacement power factor values:

True power factor includes harmonic content.

Displacement power factor only considers the fundamental frequency.

PF lead / lag convention

The meter correlates leading power factor (PF lead) or lagging power factor (PF lag) with whether the current waveform is leading or lagging the voltage waveform.

Current phase shift from voltage

For purely resistive loads the current waveform is in phase with the voltage waveform.

For capacitive loads, current leads voltage. For inductive loads, current lags voltage.

Current lead / lag and load type

Current and voltage in phase (resistive)

V

Vb

 

Ib

I

Ia Va

 

 

Ic

 

Vc

Current leads voltage (capacitive)

V

Vb

IbIa

Va

I

Ic

Vc

Current lags voltage (inductive)

V

Vb

Ib

Va

IcIa

I

Vc

90°270°

90°270°

90°270°

136

HRB1684301-01