Chapter 10—Alarms

PowerLogic™ PM5500 series user manual

 

 

Digital alarms

Digital alarms monitor the ON or OFF state of the meter’s digital inputs (S1 to S4).

Digital alarms

Alarm label

Description

 

 

Digital Alarm S1

Digital input 1

 

 

Digital Alarm S2

Digital input 2

 

 

Digital Alarm S3

Digital input 3

 

 

Digital Alarm S4

Digital input 4

 

 

Digital alarm with setpoint delay

To prevent false triggers from erratic signals, you can set up a time delay for the digital alarm.

Adding setpoint delays to a digital alarm

1

 

ΔT1

ΔT2

 

0

 

 

ΔT3

EV1

EV2

APickup setpoint (1 = ON)

BDropout setpoint (0 = OFF)

∆T1 Pickup time delay (in seconds)

EV1 Start of alarm condition

∆T2

Dropout time delay (in seconds)

EV2

End of alarm condition

∆T3

Alarm duration (in seconds)

NOTE: To prevent filling the alarm log with nuisance alarm trips, the digital alarm is automatically disabled if the digital input changes state more than 4 times in one second or more than 10 times in ten seconds. See “Digital input setup” on page 72 to adjust the Debounce setting for the digital inputs.

Standard alarms

Standard (1-Sec) alarms have a detection rate equal to the 50/60 meter cycle, which is nominally 1 second if the meter’s frequency setting is configured to match the system frequency (50 or 60 Hz). These setpoint-driven alarms monitor certain behaviors, events or unwanted conditions in your electrical system.

Many of the standard alarms are three-phase alarms. Alarm setpoints are evaluated for each of the three phases individually, but the alarm is reported as a single alarm. The alarm pickup occurs when the first phase exceeds the alarm pickup magnitude for the pickup time delay. The alarm is active as long as any phase remains in an alarm state. The alarm dropout occurs when the last phase drops below the dropout magnitude for the dropout time delay.

Standard (1-Sec) alarms

Alarm label

 

Valid range and resolution1

Units

ION Setup

Meter display

ION Setup

Meter display

 

 

 

 

 

 

Over Phase Current

Over Current, Ph

0.000 to 99999.000

0 to 99999

A

 

 

 

 

 

Under Phase Current

Under Current, Ph

0.000 to 99999.000

0 to 99999

A

 

 

 

 

 

Over Neutral Current

Over Current, N

0.000 to 99999.000

0 to 99999

A

 

 

 

 

 