Chapter 14—Maintenance and upgrades

PowerLogic™ PM5500 series user manual

 

 

21.The Firmware Update Group shows the connection name, the firmware version and status (should be “Queued”). The Group Device List shows the device or devices being upgraded. Click Download.

NOTE: A warning message displays, “Warning: Relays on PowerLogic Metering Devices will be de-energized if selected for download and will remain in this mode until a successful download is completed. Press OK to start the download.”

22.Click OK.

The Firmware Upgrade Group status changes to Active, then updates to show the current upgrade progress (in percent complete).

The Group Device List status shows “Entering Download Mode”, then changes to “Downloading” when the firmware is being downloaded to the meter. “Estimated Time Remaining” shows the firmware download progress.

You can also check the progress on meters equipped with a display panel. The meter display shows “Download in progress” and a shows a dynamically incrementing number for “Percent Complete” (up to 100%).

23.When the firmware upgrade is complete, the Firmware Update Group status shows Complete (Passed). The Group Device List status shows Successful Download. Click Finished.

24.To exit the download firmware program, click Yes when prompted to quit DLF.

Upgrading the Ethernet card

The Ethernet card is the hardware component in your meter that is responsible for Ethernet communications. The Ethernet files are contained in two folders: FW and www:

FW contains the code and other initialization files that run Ethernet communications.

www contains the webpages and java script files. You can add custom webpages or modify the existing ones in this folder.

To upgrade your Ethernet card firmware, use an FTP client, such as FileZilla.

1.Start your FTP client.

2.Click Edit > Settings.

3.In the tree view, click Transfers > File Types.

4.Set Default transfer type to Binary, then click OK.

5.Type the meter’s IP address in the Host field and log in using your credentials. The factory default settings are:

Username = user2

Password = pass2

6.You may leave the Port field blank (the default FTP port setting is 21). Click Quickconnect.

7.In the local site pane, navigate to the folder where you downloaded the communications card firmware, then open the FW folder.

8.Navigate to the FW folder in the remote site pane (i.e., the meter).

9.Select all files in the FW folder from the local site, then upload it to the FW folder on the remote site.

10.If prompted that the target file already exists, select or confirm to overwrite the target file. Select Apply to current queue only if this option exists in the FTP client you are using.

11.Repeat the previous file transfer steps, this time selecting all files in the www folder.