Chapter 13—Power qualityPowerLogic™ PM5500 series user manual

Power Quality display screens (Continued)

IEEE mode

IEC mode

Description

 

 

 

K-F B

K-F B

K factor for phase B

 

 

 

K-F C

K-F C

K factor for phase C

 

 

 

2.

Navigate to Harm > Crest. The Crest factor information displays.

 

Crest Factor display screens

 

 

 

 

 

 

 

 

IEEE mode

IEC mode

Description

 

 

 

 

 

 

 

V L-L

U

Crest factor data for line-to-line voltage

 

 

 

 

 

 

 

V L-N

V

Crest factor data for line-to-neutral voltage

 

 

 

 

 

 

 

Amps

I

Crest factor data for current

 

 

 

 

 

3.

Press to return to the main display screens.

 

NOTE: Your meter’s Modbus map includes registers for harmonics data for

 

integration into your power or energy management system.

Related topics

See “Front panel display and meter setup” on page 31 for front panel menu navigation details.

Search your meter’s Modbus register list at www.schneider-electric.com to download the Modbus map.

Viewing THD/thd using the front panel

You can view THD/thd data using the front panel.

1.

Navigate to THD. On the THD/thd Select screen, press THD to display values that

 

use the calculation method based on the fundamental harmonic, or thd to display

 

values that use the calculation method based on the RMS value of all harmonics in

 

that phase (including the fundamental).

 

THD (or thd) display screens

 

 

 

 

 

 

 

 

IEEE mode

IEC mode

Description

 

 

 

 

 

 

 

Amps

I

Total harmonic distortion data for per phase and neutral currents.

 

 

 

 

 

 

 

V L-L

U

Total harmonic distortion data line-to-line voltage.

 

 

 

 

 

 

 

V L-N

V

Total harmonic distortion data line-to-neutral voltage.

 

 

 

 

 

2.

Press the current or voltage THD or thd values you want to view. The total harmonic

 

distortion percentage values are displayed.

3.

Press to return to the main display screens.

NOTE: Your meter’s Modbus map includes registers for total harmonic distortion data for integration into your power or energy management system.

Related topics

See “Front panel display and meter setup” on page 31 for front panel menu navigation details.

Search your meter’s Modbus register list at www.schneider-electric.com to download the Modbus map.