E5ZE Temperature Controller Write Protocol

Appendix F

 

 

 

Write Set Point (Setting Unit 0.1) (Sequence No. 151)

Writes the set points using a setting unit of 0.1 (5 digits).

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

 

send data

+1

 

 

 

 

 

 

+2

 

 

 

 

 

 

+3

 

 

+4

 

 

 

 

+5

 

 

~

 

+16

 

 

 

 

+17

 

Number of send data words

(Undefined) Unit No.

Set point (rightmost 4 digits)

Set point (leftmost 1 digit)

Set point (rightmost 4 digits)

Set point (leftmost 1 digit)

~

Set point (rightmost 4 digits)

Set point (leftmost 1 digit)

Channel 0

Channel 1

Channel 7

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0018 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits Hex)

00 to 0F

 

 

 

+2

Channel 0

Varies according to the temperature sensor

 

Set point (rightmost 4 digits)

type. Refer to the manual for the E5ZE.

 

(4 digits BCD)

 

 

 

 

+3

Channel 0

 

 

Set point (leftmost 1 digit)

 

 

(1 digit BCD)

 

 

 

 

 

D

 

 

D

 

 

D

 

 

 

 

+16

Channel 7

Varies according to the temperature sensor

 

Set point (rightmost 4 digits)

type. Refer to the manual for the E5ZE.

 

(4 digits BCD)

 

 

 

 

+17

Channel 7

 

 

Set point (rightmost 1 digit)

 

 

(1 digit BCD)

 

 

 

 

Receive Data Word Allocation (3rd Operand of PMCR)

None.

Note When the setting unit for the set point is 1 (4 digits), use Write Set Point (Setting Unit 1), Sequence No.150.