Using Protocol Macros

 

Section 5-1

 

 

 

 

 

 

 

Item

 

Description

 

 

 

 

 

 

Sequence contents

 

Number of steps

16 max.

 

 

(step common

 

per sequence

 

 

 

parameters)

 

 

 

 

 

 

Transmission

X-on/X-off flow, RTS/CTS flow, delimiter control, or contention control,

 

 

 

 

control

and modem control can be selected.

 

 

parameters

 

 

 

 

 

 

 

 

 

 

Response

Scan notification or interrupt notification (i.e., writing the receive data in

 

 

notification

the I/O memory area specified in the 3rd operand of the PMCR(––)

 

 

method (operand)

instruction) can be selected.

 

 

 

Scan notification:

 

 

 

 

 

Writes the receive data to I/O memory during CPU Unit scanning.

 

 

 

Interrupt notification:

 

 

 

 

 

Writes the receive data to I/O memory as soon as it is received, and at

 

 

 

the same time specifies the execution of the interrupt program for the

 

 

 

CPU Unit.

 

 

 

 

 

 

 

 

 

 

Scan method

Yes

 

 

 

(fixed)

 

 

 

 

 

 

 

 

 

 

Interrupt

Yes

 

 

 

notification

 

 

 

 

 

Interrupt

Yes

 

 

 

notification for

 

 

 

 

 

reception case

 

 

 

 

 

number

 

 

 

 

 

 

 

 

 

Monitoring time

Receive wait, receive completion, or send completion can be

 

 

during

monitored.

 

 

 

 

send/receive

Setting range: 0.01 to 0.99 s, 0.1 to 9.9 s, 1 to 99 s, or 1 to 99 min

 

 

processing

 

 

 

 

 

 

 

 

 

 

 

Link word setting

Area in which data is exchanged between the CPU Unit and the Serial

 

 

 

Communications Board during Serial Communications Board

 

 

 

refreshing. Two areas are possible for each device: An area for storing

 

 

 

receive data and an area for storing send data.

60

Page 71