PC Setup Settings

 

 

Section 3-3

 

 

 

 

 

 

Word

Bits

 

Function

Communications

 

 

 

 

 

modes

IR 202

00 to 07

Port 1

Communicating with PT Flags (Bits 00 to 07 are flags for PTs 0 to 7.)

NT Link in 1:N mode

 

 

 

 

 

 

 

 

Repeat counter PV (00 to FF hexadecimal)

Protocol macro

 

 

 

 

 

 

 

00 to 15

 

Reception counter

 

No-protocol

 

 

 

The number of bytes of data received in No-protocol Mode (Hex). Reset

 

 

 

 

 

to 0 when data is read out using RXD(––).

 

 

IR 203

00 to 07

Port 2

Communicating with PT Flags (Bits 00 to 07 are flags for PTs 0 to 7.)

NT Link in 1:N mode

 

 

 

 

 

 

 

 

Repeat counter PV (00 to FF hexadecimal)

Protocol macro

 

 

 

 

 

 

 

00 to 15

 

Reception counter

 

No-protocol

 

 

 

The number of bytes of data received in No-protocol Mode (Hex). Reset

 

 

 

 

 

to 0 when data is read out using RXD(––).

 

 

 

 

 

 

 

 

IR 204

00

Port 1

Tracing Flag

 

Protocol macro

 

 

 

 

 

 

 

 

01

Port 2

 

 

 

 

 

 

 

 

 

 

 

 

02 to 07

Not used.

 

 

 

 

 

 

 

 

 

 

08 to 11

Port 1

Protocol Macro Error Code

 

 

 

 

 

 

0: Normal operation

1: No protocol macro function

 

 

 

 

 

2: Sequence number error

3: Data read/write area overflow

 

 

 

12 to 15

Port 2

 

 

 

4: Protocol data grammar error

 

 

 

 

 

5: Protocol macro execution error during port initialization

 

 

 

 

 

 

 

IR 205

00 to 03

Port 1

Completed Reception Case Number

Protocol macro

 

 

 

 

 

 

 

 

04 to 07

 

Completed Step Number

 

 

 

 

 

 

 

 

 

 

 

08 to 14

 

Not used.

 

 

 

 

 

 

 

 

 

 

15

 

IR 204 (bits 08 to 11) Data Stored Flag

 

 

 

 

 

0: No data stored; 1: Data stored

 

 

IR 206

00 to 03

Port 2

Completed Reception Case Number

Protocol macro

 

 

 

 

 

 

 

 

04 to 07

 

Completed Step Number

 

 

 

 

 

 

 

 

 

 

 

08 to 14

 

Not used.

 

 

 

 

 

 

 

 

 

 

15

 

IR 204 (bits 12 to 15) Data Stored Flag

 

 

 

 

 

0: No data stored; 1: Data stored

 

 

 

 

 

 

 

IR 207

00

Port 1

Serial Communications Port Restart Bits

All modes

 

 

 

 

 

 

 

 

01

Port 2

 

 

 

 

 

 

 

 

 

 

02

Port 1

Continuous Trace Start/Stop Bits

Protocol macro

 

 

 

 

 

 

 

 

03

Port 2

 

 

 

 

 

 

 

 

 

 

 

 

04

Port 1

Shot Trace Start/Stop Bits

 

 

 

 

 

 

 

 

 

 

 

05

Port 2

 

 

 

 

 

 

 

 

 

 

 

 

06 to 07

Not used.

 

 

 

 

 

 

 

 

08

Port 1

Protocol Macro Executing Flag (instruction execution)

No-protocol or

 

 

 

 

 

Protocol macro

 

 

 

 

 

 

09

 

Transfer Step Error Processing Flag

Protocol macro

 

 

 

 

 

 

 

10

 

Sequence End Completion Flag

 

 

 

 

 

 

 

 

 

 

11

 

Forced Abort Bit

 

 

 

 

 

 

 

 

 

12

Port 2

Protocol Macro Executing Flag (instruction execution)

No-protocol or

 

 

 

 

 

Protocol macro

 

13

 

Transfer Step Error Processing Flag

Protocol macro

 

 

 

 

 

 

 

14

 

Sequence End Completion Flag

 

 

 

 

 

 

 

 

 

 

15

 

Forced Abort Bit

 

 

 

 

 

 

 

 

 

 

IR 208

00 to 15

Not used.

 

---

 

to

 

 

 

 

 

 

IR 215

 

 

 

 

 

 

31