CompoWay/F Master Protocol

Appendix B

 

 

Command Frame Contents

 

 

 

 

 

 

 

 

 

 

 

Item

Meaning

 

 

 

 

 

 

 

 

 

STX

A code, 02 Hex, indicating the beginning of a communications

 

 

 

 

 

frame (text). This code must always be set as the first byte.

 

 

 

 

 

 

 

 

 

Node number

The node number identifies the source of the command frame.

 

 

 

 

 

Specify “XX” to broadcast a transmission. There will be no response

 

 

 

 

 

made to a broadcast.

 

 

 

 

 

 

 

 

 

Subaddress

Set “00” for most components. Other values must be set for special

 

 

 

 

 

components.

 

 

 

 

 

 

 

 

 

SID

Set “0” for most components. Other values must be set for special

 

 

 

 

 

components.

 

 

 

 

 

 

 

 

 

Command and text

The command and required text are placed here. Refer to the

 

 

 

 

 

command codes and text for individual sequences.

 

 

 

 

 

 

 

 

 

 

MRC and SRC

The command code specifies the service being used. Refer to the

 

 

 

 

 

command codes and text for individual sequences.

 

 

 

 

 

 

 

 

 

ETX

A code, 03 Hex, indicating the end of text.

 

 

 

 

 

 

 

 

BCC

The block check character (horizontal parity, 1 byte). The character

 

 

 

 

 

is an exclusive OR of all data from just after the STX to the ETX.

 

 

 

 

 

 

 

 

Response Frame Contents

 

 

 

 

 

 

 

 

 

 

 

Item

Meaning

 

 

 

 

 

 

 

 

STX

A code, 02 Hex, indicating the beginning of a communications

 

 

 

 

 

frame (text). This code must always be set as the first byte.

 

 

 

 

 

 

 

 

Node number

The node number identifies the source of the command frame. “XX”

 

 

 

 

 

is specified to broadcast a transmission. There will be no response

 

 

 

 

 

made to a broadcast.

 

 

 

 

 

 

 

 

Subaddress

“00” for most components. Other values must be set for special

 

 

 

 

 

components.

 

 

 

 

 

 

 

 

SID

“0” for most components. Other values must be set for special

 

 

 

 

 

components.

 

 

 

 

 

 

 

 

End code (See note.)

The results of executing the command frame.

 

 

 

 

 

Note: The response code (MRES and SRES) indicates the results

 

 

 

 

 

for the command code; the end code indicates the results for the

 

 

 

 

 

command frame. These are not the same.

 

 

 

 

 

 

 

 

Response and text

The response and requested text are placed here. Refer to the

 

 

 

 

 

response and text for individual sequences.

 

 

 

 

 

 

 

 

 

 

MRES and SRES

The response code specifies the results of processing the service

 

 

 

 

 

requested by the command code. Refer to the response codes and

 

 

 

 

 

text for individual sequences.

 

 

 

 

 

 

 

 

 

ETX

A code, 03 Hex, indicating the end of text.

 

 

 

 

 

 

 

 

BCC

The block check character (horizontal parity, 1 byte). The character

 

 

 

 

 

is an exclusive OR of all data from just after the STX to the ETX.

 

 

 

 

 

 

 

139

Page 146
Image 146
Omron CQM1H-SCB41 operation manual Appendix B, Command Frame Contents, Response Frame Contents