Connections

Section 8-2

6.With some PTs, timeout settings can be changed to eliminate some of the communications errors. Refer to the operation manual for the PT for details. This is true in both 1:1 and 1:N mode.

7.If more PTs are required by the system than allowed by the above restric- tions in 1:N mode, connect the PTs in smaller groups to different ports.

8-2 Application Procedure

1, 2, 3... 1. Turn OFF the power supply to the PC.

2.Mount the Board.

3.Connections

Connect the external devices using RS-232C or RS-422 cables. The TERM and WIRE switches on the front panel of the Board must be set if the Board is connected using the RS-422A/485 port.

The CPU Unit can be connected to a Programming Console, the CX-Pro- grammer, or the CX-Protocol as required.

4.Turn ON power.

5.Set the PC Setup settings for the Serial Communications Board.

Use a Programming Console, the CX-Programmer, or the CX-Protocol to set the settings in the PC Setup between DM 6550 and DM 6559.

Note The settings stored in these words are read constantly; the PC does not need to be restarted or reset when changes are made to the set- tings. They will be updated automatically as soon as they are changed.

NT Link Settings for 1:N Mode

The following table shows the settings for connecting more than one PT when the highest PT unit number is 5.

Port 1

Port 2

Bit(s)

Setting

Function

 

 

 

 

 

DM 6555

DM 6550

00 to 07

---

Not used.

 

 

 

 

 

 

 

08 to 11

5 (BCD)

Maximum Programmable

 

 

 

 

Terminal unit number

 

 

 

 

1 to 7 (BCD)

 

 

 

 

NT Link in 1:N mode

 

 

 

 

 

 

 

12 to 15

5 Hex

Communications mode

 

 

 

 

NT Link in 1:N mode

 

 

 

 

 

DM 6556

DM 6551

00 to 15

---

Not used.

 

 

 

 

 

DM 6557

DM 6552

00 to 15

 

 

 

 

 

 

 

DM 6558

DM 6553

00 to 15

 

 

 

 

 

 

 

DM 6559

DM 6554

00 to 15

 

 

Port Settings are always the same for 1:N-mode NT Links. Settings of the start bits, stop bits, parity, and baud rate are not necessary and will be ig- nored.

Set the communications mode to a 1:N-mode NT Link (5 Hex).

Up to 8 PTs can be connected in 1:N mode. Set the highest unit number of the PTs to be connected as the maximum Programmable Terminal unit num- ber.

NT Link Settings for 1:1 Mode

The following table shows the settings for a 1:1-mode NT Link.

Port 1

Port 2

Bit(s)

Setting

Function

 

 

 

 

 

DM 6555

DM 6550

00 to 11

---

Not used.

 

 

 

 

 

 

 

12 to 15

4 Hex

Communications mode

 

 

 

 

NT Link in 1:1 mode

116