Omron CQM1H-SCB41 operation manual Switch to Level 1 Sequence No, Software Reset Sequence No

Models: CQM1H-SCB41

1 421
Download 421 pages 6 Kb
Page 192
Image 192

E5jK Digital Controller Write Protocol

Appendix D

 

 

 

Switch to Level 1 (Sequence No. 075)

Switches the setting level to level 1 (setup mode, extended mode). This sequence can be executed for multiple units.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

 

Number of send data words

 

send data

 

 

 

 

 

+1

 

Number of units

 

 

 

 

 

 

 

 

 

 

 

+2

 

(Undefined)

Unit No.

 

 

 

 

 

 

 

 

 

 

 

+3

 

(Undefined)

Unit No.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

~

 

~

+9

(Undefined)

Unit No.

(max.)

Offset

Contents (data format)

Data

+0

Number of send data words

Number of units + 2

 

(4 digits BCD)

 

+1

Number of units (4 digits BCD)

0001 to 0008

+2 to 9 Unit No. (2 digits BCD)

00 to 31

Receive Data Word Allocation (3rd Operand of PMCR)

None.

Software Reset (Sequence No. 076)

Resets the operation of the E5jK (equivalent to turning on the power supply). This sequence can be executed for multiple units.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

 

Number of send data words

 

send data

 

 

 

 

 

+1

 

Number of units

 

 

 

 

 

 

 

 

 

 

 

+2

 

(Undefined)

Unit No.

 

 

 

 

 

 

 

 

 

 

 

+3

 

(Undefined)

Unit No.

 

 

 

 

 

 

 

 

~

 

~

+9

(Undefined)

Unit No.

(max.)

Offset

Contents (data format)

Data

+0

Number of send data words

Number of units + 2

 

(4 digits BCD)

 

+1

Number of units (4 digits BCD)

0001 to 0008

+2 to 9 Unit No. (2 digits BCD)

00 to 31

Receive Data Word Allocation (3rd Operand of PMCR)

None.

Note Communications with the E5jK are disabled for about five seconds after this sequence is executed.

185

Page 192
Image 192
Omron CQM1H-SCB41 operation manual Switch to Level 1 Sequence No, Software Reset Sequence No