Omron CQM1H-SCB41 operation manual Read Set Point, Process Value, and Output Value Sequence No

Models: CQM1H-SCB41

1 421
Download 421 pages 6 Kb
Page 200
Image 200

E5ZE Temperature Controller Read Protocol

Appendix E

 

 

 

 

 

 

 

 

 

Offset

Contents (data format)

Data

 

 

 

 

 

 

 

 

+0

Number of receive data words

0017

 

 

 

 

(4 digits BCD)

 

 

 

 

 

 

 

 

 

+1

Channel 0

0000 to 1000

 

 

 

 

Output value (4 digits BCD)

 

 

 

 

 

 

 

 

 

+2

Channel 0

0000 to 1000

 

 

 

 

Cooling output value (4 digits BCD)

 

 

 

 

 

 

 

 

 

+3

Channel 1

0000 to 1000

 

 

 

 

Output value (4 digits BCD)

 

 

 

 

 

 

 

 

 

+4

Channel 1

0000 to 1000

 

 

 

 

Cooling output value (4 digits BCD)

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

D

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

+15

Channel 7

0000 to 1000

 

 

 

 

Output value (4 digits BCD)

 

 

 

 

 

 

 

 

 

+16

Channel 7

0000 to 1000

 

 

 

 

Cooling output value (4 digits BCD)

 

 

 

 

 

 

 

 

Read Set Point, Process Value, and Output Value (Sequence No. 103)

Reads the set points, process values, and output values and stores the results in the specified words.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0002 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits Hex)

00 to OF

Receive Data Word Allocation (3rd Operand of PMCR)

Receive data

+0

 

storage words

+1

 

 

 

 

 

 

+2

 

 

+3

 

 

+4

 

 

 

 

+5

 

 

~

 

+36

 

 

+37

 

 

+38

 

 

+39

 

 

+40

 

Number of receive data words

Set point (rightmost 4 digits)

Set point (leftmost 1 digit)

Process value (rightmost 4 digits)

Process value (leftmost 1 digit)

Output value

~

Set point (rightmost 4 digits)

Set point (leftmost 1 digit)

Process value (rightmost 4 digits)

Process value (leftmost 1 digit)

Output value

Channel 0

Channel 7

194

Page 200
Image 200
Omron CQM1H-SCB41 operation manual Read Set Point, Process Value, and Output Value Sequence No