Board Replacement

 

 

 

Section 9-2

 

 

 

 

 

 

 

Serial com-

Indicator

Status

I/O memory

Cause

Remedy

munications

status

information,

 

 

 

 

mode

 

etc.

 

 

 

 

 

 

 

 

 

 

Serial commu-

---

---

Bits 12 to 15 (Serial

Serial communica-

Set bits 12 to 15 of

nications mode

 

 

Communications

tions mode is not

DM 6555/DM 6550 to

is not set to

 

 

Mode) of

set correctly.

0 Hex. (Host Link).

Host Link.

 

 

DM 6555/DM 6550

 

 

 

 

 

 

are set to a value

 

 

 

 

 

 

other than 0 Hex.

 

 

 

 

 

 

 

 

 

Serial commu-

The COMMj

---

---

Cables are incor-

Check the wiring.

nications mode

indicators do

 

 

rectly connected.

 

 

is set to Host

not flash at all.

 

 

The RS-422A/485

Reset the port to the cor-

Link.

(Communica-

 

 

 

 

port setting (2-wire

rect wiring setting.

 

tions have not

 

 

 

 

 

or 4-wire) is incor-

Wire all nodes using the

 

been electrical-

 

 

 

 

 

rect (WIRE).

 

ly established.)

 

 

4-wire method.

 

 

 

Adapters such as

 

 

 

 

 

 

 

 

 

 

the NT-AL001-E

 

 

 

 

 

 

are incorrectly

 

 

 

 

 

 

wired or set.

 

 

 

 

 

 

 

 

 

 

 

 

Commands are not

Reset the serial commu-

 

 

 

 

being set from the

nications port at the host,

 

 

 

 

host.

and rewrite the program.

 

 

 

 

 

 

 

 

 

 

There is a hard-

Replace the Serial Com-

 

 

 

 

ware error.

munications Board.

 

 

 

 

 

 

 

The COMMj

There is no

IR 20100 to

The PC Setup set-

Reset the settings in the

 

indicators are

transmission

IR 20103 or

tings for the Host

PC Setup for the Host

 

flashing, but

error.

IR 20108 to

Link unit No., Host

Link unit No., Host Link

 

the response

 

IR 20177 are

Link transmission

transmission delay and

 

has not been

 

0 Hex.

delay, or other set-

other settings so that they

 

returned to the

 

 

tings do not match

match the settings at the

 

host. (Commu-

 

 

the settings for the

host device.

 

nications have

 

 

remote device.

Correct the command

 

been electrical-

 

 

 

 

 

 

The command for-

frame (header, Host Link

 

ly established.)

 

 

 

 

 

mat and data

Unit No., terminator, etc.)

 

 

 

 

 

 

 

 

length of the data

and the program.

 

 

 

 

sent from the host

 

 

 

 

 

 

are incorrect.

 

 

 

 

 

 

 

 

 

 

 

---

Cables are incor-

Check the wiring and

 

 

 

 

rectly connected.

switch settings, and cor-

 

 

 

 

The RS-422A/485

rect if necessary.

 

 

 

 

 

 

 

 

 

 

port setting (2-wire

 

 

 

 

 

 

or 4-wire) is incor-

 

 

 

 

 

 

rect (WIRE).

 

 

 

 

 

 

Adapters such as

 

 

 

 

 

 

the NT-AL001-E

 

 

 

 

 

 

are incorrectly

 

 

 

 

 

 

wired or set.

 

 

 

 

 

 

 

 

 

 

 

---

This is a transmis-

Conduct a loopback test

 

 

 

 

sion circuit hard-

in serial communications

 

 

 

 

ware error.

mode to check the trans-

 

 

 

 

 

mission lines. If an error

 

 

 

 

 

occurs during the test, re-

 

 

 

 

 

place the Serial Commu-

 

 

 

 

 

nications Board.

 

 

 

 

 

 

 

 

 

 

The send delay

Reset the parameters in

 

 

 

 

time setting is too

the PC Setup correctly.

 

 

 

 

long.

 

 

122

Page 130
Image 130
Omron CQM1H-SCB41 operation manual 122