Appendix D

E5jK Digital Controller Write Protocol

The E5jK Digital Controller Write Protocol writes and controls various settings in remote mode for the Controller connected to the Serial Communications Board via RS-232C or RS-485 cable.

Note Negative values cannot be written. All values must be set as unsigned BCD.

Structure of the Protocol

The following table shows the structure of the E5jK Digital Controller Write Protocol.

Sequence

Communications

Function

 

Ladder interface

No.

sequence name

 

 

 

 

 

 

Send word

Receive word

 

 

 

 

 

 

 

 

allocation

allocation

 

 

 

 

 

 

050

Write set point

Writes the set point.

 

Yes

No

 

 

 

 

 

 

051

Write alarm value

Writes alarm value 1, 2.

 

Yes

No

 

 

 

 

 

 

052

Write proportional band,

Writes the proportional band, integral

 

Yes

No

 

integral time, and deriva-

time, and derivative time.

 

 

 

 

tive time

 

 

 

 

 

 

 

 

 

 

053

Write cooling coefficient

Writes the cooling coefficient.

 

Yes

No

 

 

 

 

 

 

054

Write dead band

Writes the dead band.

 

Yes

No

 

 

 

 

 

 

055

Write manual reset value

Writes the manual reset value.

 

Yes

No

 

 

 

 

 

 

056

Write hysteresis

Writes the hysteresis (heating, cooling)

 

Yes

No

 

 

 

 

 

 

057

Write control period

Writes the control period (heating, cool-

 

Yes

No

 

 

ing)

 

 

 

058

Write SP ramp time units

Writes the SP ramp time unit and SP

 

Yes

No

 

and set value

ramp set value.

 

 

 

 

 

 

 

 

 

059

Write LBA detection time

Writes the LBA detection time.

 

Yes

No

 

 

 

 

 

 

060

Write MV at stop time and

Writes the MV at stop and the MV at PC

 

Yes

No

 

PV error

error.

 

 

 

 

 

 

 

 

 

061

Write MV limits

Writes the MV limits.

 

Yes

No

 

 

 

 

 

 

062

Write input digital filter

Writes the input digital filter.

 

Yes

No

 

 

 

 

 

 

063

Write alarm hysteresis

Writes alarm 1, 2 hysteresis.

 

Yes

No

 

 

 

 

 

 

064

Write input shift values

Writes the input shift values.

 

Yes

No

 

 

 

 

 

 

065

Write level 0 parameters

Writes parameters in level 0.

 

Yes

No

 

 

 

 

 

 

066

Write level 1 parameters 1

Writes parameters in level 1.

 

Yes

No

 

 

 

 

 

 

067

Write level 1 parameters 2

Writes parameters in level 1.

 

Yes

No

 

 

 

 

 

 

068

Write level 2 parameters 1

Writes parameters in level 2.

 

Yes

No

 

 

 

 

 

 

069

Write level 2 parameters 2

Writes parameters in level 2.

 

Yes

No

 

 

 

 

 

 

070

General-purpose write

Writes the value of the specified parame-

 

Yes

No

 

 

ter.

 

 

 

071

Switch to level 0 (software

Switches the setting level to level 0.

 

Yes

No

 

reset)

 

 

 

 

072

Run/stop

Initiates Run or Stop.

 

Yes

No

 

 

 

 

 

 

073

Remote/local

Switches the mode to remote or local

 

Yes

No

 

 

mode.

 

 

 

 

 

 

 

 

 

074

Execute/cancel AT

Executes or cancels AT.

 

Yes

No

 

 

 

 

 

 

075

Switch to level 1

Switches the setting level to level 1.

 

Yes

No

 

 

 

 

 

 

076

Software reset

Resets the E5jK.

 

Yes

No

Note Ladder Interface Settings

 

 

 

 

YES:

User settings are required for the 2nd or 3rd operands of PMCR.

 

 

NO:

Send word allocation:

Set the constant 0000 for the 2nd operand (S).

 

 

Receive word allocation: Set a dummy word (e.g., DM 0000) address for the 3rd operand (D).