ConnectionsSection 4-2

4-1-2 Host Link Specifications

Item

 

 

 

Description

 

 

 

 

Communications mode

Half-duplex (Full-duplex for slave-initiated communications)

 

 

 

 

 

Synchronization

Start-stop (asynchronous mode)

 

 

 

 

 

 

 

Baud rate (see note 1)

RS-232C port and RS-422A/485 ports:

 

 

 

1,200/2,400/4,800/9,600/19,200 bps

 

 

 

Default setting: 9,600 bps

 

 

 

 

 

 

 

Communications

RS-232C port: 15 m max. (see note 2)

 

 

distance (see note 1)

RS-442A/485 port: 500 m max. (The total combined cable length is 500 m max. T-branch

 

 

lines must be a maximum of 10 m long.)

 

 

 

 

 

 

Connection

RS-232C port: 1:1 (1:N (N = 32 Units max.) is possible using an Converting Link Adapters.)

configuration

RS-422A/485 port: 1:N (N = 32 Units max.)

 

 

 

 

 

Number of connected

32 Units max. (unit numbers 0 to 31; unit number 0 is set for 1:1 connection)

Units

 

 

 

 

 

Frame structure

C-mode Host Link commands

 

 

 

Header:

@, address: (Host Link unit number) 0 to 31 (BCD)

 

Data:

Header code + text

 

 

 

Error check code: FCS

 

 

 

Terminator:

*+CR

 

 

Error check codes

Vertical parity: Even, odd. or none

 

 

 

FCS (horizontal parity converted to ASCII)

 

 

 

 

 

 

Command flow and

Command flow

 

Commands

 

Contents

support

 

 

 

 

 

Host computer to

 

C-mode Host Link

 

1:1 or 1:N communications with directly connected

 

 

 

 

PC

 

commands

 

PCs (The specified frame format must be prepared

 

 

 

 

 

on the host computer and then sent.)

 

 

 

 

 

 

 

PC to host

 

Data only

 

Communications using TXD(––) from CPU Unit.

 

computer

 

 

 

No response from host.

 

 

 

 

 

 

 

 

 

 

Connection between the host computer and PC

 

 

 

 

 

must be 1:1.

 

 

 

 

 

Transmission delay

Host computer to PC

 

0 to 99,990 ms (set in PC Setup in 10-ms units)

time

The delay is from the return of a

 

 

 

 

 

 

response by the PC until a response

 

 

 

can be returned to the next command

 

 

 

received from the host.

 

 

 

PC to host computer

 

 

 

The delay is from the beginning of

 

 

 

TXD(––) execution until execution of

 

 

 

the next TXD(––) can be started.

 

 

 

 

 

 

 

Note 1. Confirm the baud rates and communications distance supported by con-

 

nected devices.

 

 

 

2. The maximum cable length for RS-232C is 15 m.

4-2 Application Procedure

1, 2, 3... 1. Turn OFF the power supply to the PC.

2.Mount the Board.

3.Connections

Connect the external devices using RS-232C or RS-422 cables. The TERM and WIRE switches on the front panel of the Board must be set if the Board is connected using the RS-4522A/485 port.

The host computer can be connected to a PC 1:1, or NT-AL001-E Convert- ing Link Adapters can be used to convert from RS-232C to RS-422A/485 to connect the host computer to PCs 1:N. Standard connection examples are

36