E5jK Digital Controller Read Protocol

Appendix C

 

 

 

Read MV at Stop Time and at PV Error (Sequence No.013)

Reads the MV at stop time and at PV error and stores the results in the specified words.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0002 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits BCD)

00 to 31

Receive Data Word Allocation (3rd Operand of PMCR)

Receive data

+0

storage words

+1

 

 

+2

Number of receive data words

MV at stop time

MV at PV error

Offset

Contents (data format)

Data

 

 

 

+0

Number of receive data words

0003

 

(4 digits BCD)

 

 

 

 

+1

MV at stop time (4 digits BCD)

F050 to 1050

 

 

F indicates a negative value.

 

 

A050 to 1050 for heating/cooling control

 

 

A indicates a negative value.

 

 

 

+2

MV at PV error (4 digits BCD)

F050 to 1050

 

 

F indicates a negative value.

 

 

 

Read MV Limits (Sequence No. 014)

Reads the MV upper limit, MV lower limit, and MV change rate limit and stores the results in the specified words.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0002 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits BCD)

00 to 31

Receive Data Word Allocation (3rd Operand of PMCR)

Receive data

+0

Number of receive data words

storage words

 

 

+1

MV upper limit

 

 

 

 

 

+2

MV lower limit

 

 

 

 

+3

MV change rate limit

 

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of receive data words

0004

 

(4 digits BCD)

 

 

 

 

+1

MV upper limit (4 digits BCD)

MV lower limit + 1 to 1050

 

 

0000 to 1050 for heating/cooling control

 

 

 

+2

MV lower limit (4 digits BCD)

F050 to MV upper limit –1

 

 

F indicates a negative value values.

 

 

A050 to 1050 for heating/cooling control

 

 

A indicates a negative value.

 

 

 

+3

MV change rate limit

0000 to 1000

 

(4 digits BCD)

 

 

 

 

161