OverviewSection 7-1

7-1

Overview

 

 

 

 

 

 

 

 

 

If two PCs are linked one-to-one by connecting them together through RS-232C

 

or 4-wire RS-422A/485 cable, they can share up to 64 words of their LR areas.

 

The 1:1 Data Links are the same as normal Data Links in that data is not shared

 

bidirectionally, i.e., the link words written by one PC are transferred to the other

 

PC.

 

 

 

 

 

 

 

 

 

One of the following three ranges of words can be set to be linked:

 

LR 00 to LR 63, LR 00 to LR 31, or LR 00 to LR 15

 

A 1:1 Data Link communications system can be created between the CQM1H

 

and another CQM1H, or between the CQM1H and the CQM1, C200HX/HG/HE,

 

C200HS, CPM1, CPM1A, CPM2A, CPM2C, or SRM1(-V2).

 

One of the PCs is set as a 1:1 Data Link master and the other as a 1:1 Data Link

 

slave. The linked words are separated into two groups of words, and the words

 

written by each PC is transferred to the other PC, as illustrated in the following

 

diagram.

 

 

 

 

 

 

 

 

 

For example, if LR 00 to LR 63 are linked, the status of LR 00 to LR 31 written by

 

the master CQM1H will be transferred to LR 00 to LR 31 of the slave CQM1H,

 

and the status of LR 32 to LR 63 written by the slave CQM1H will be transferred

 

to LR 32 to LR 63 of the master CQM1H.

 

 

 

 

 

CQM1H or

 

CQM1H or other C-series PC

 

other C-series PC

 

 

 

Link

 

 

 

 

 

 

 

 

RS-232C

 

 

 

 

 

 

 

Serial Communications Board

 

 

 

 

 

 

 

 

CQM1H or

 

 

 

CQM1H or

 

 

other C-series PC

 

 

 

other C-series PC

 

LR 00

Master area

 

 

LR 00

 

 

 

 

 

to

 

 

to

 

 

Master area

 

 

(sent)

 

 

LR 31

 

 

(received)

 

 

LR 31

 

 

 

 

 

 

 

 

LR 32

 

 

 

LR 32

 

 

 

 

 

to

Slave area

 

 

to

 

 

Slave area

 

 

(received)

 

 

 

 

 

(sent)

 

 

 

 

 

LR 63

 

 

 

 

LR 63

 

 

 

 

 

 

 

The words in the LR area that will be linked are set in the PC Setup as shown in the following table.

PC Setup Setting

Port 1

Port 2

Bits

Function

Setting

Master words

Slave words

DM 6555

DM 6550

04 to 07

Link words for 1:1 link

0 Hex: LR 00 to LR 63

LR 00 to LR 31

LR 32 to LR 63

 

 

 

 

1 Hex: LR 00 to LR 31

LR 00 to LR 15

LR 16 to LR 31

 

 

 

 

2 Hex: LR 00 to LR 15

LR 00 to LR 07

LR 08 to LR 15

7-1-1 Starting Data Links

Connect two PCs one-to-one through RS-232C or 4-wire RS-422A/485 cable, make the proper settings in the PC Setup, and turn ON the power supplies. The 1:1 Data Link will start automatically.

108