V600/V620 ID Controller Protocol

Appendix M

 

 

 

Auto-read (Hexadecimal/1) (Sequence No. 509)

This sequence is used when the maximum number of Heads to be read from the Carrier is 1.

Send Data Word Allocation (2nd Operand of PMCR)

The send data word allocation is similar to that of Sequence No. 504 (Read (Hexadecimal/1)).

Receive Data Word Allocation (3rd Operand of PMCR)

The receive data word allocation is similar to that of Sequence No. 504 (Read (Hexadecimal/1)).

Note For auto-read (AR), a response is not returned if the number of Heads is not read by the Carrier, the Abort Bit must be turned OFF to terminate the sequence.

Polling Auto-read (ASCII) (Sequence No. 510)

This sequence is used when the number of Heads to be read from the Carrier is from 1 to 8.

Send Data Word Allocation (2nd Operand of PMCR)

First word of send +0

data+1

+2

+3

+4

+5

~

+(4(N–1)+2)

+(4(N–1)+3)

+(4(N–1)+4)

+(4(N–1)+5)

Number of send data words

Number of Heads

(Undefined)

 

 

Unit No.

 

 

 

(Undefined)

 

 

Head CH No.

 

 

 

 

 

 

 

 

 

 

 

 

 

Leading address No.

 

 

 

 

(Undefined)

 

Read bytes

 

 

 

 

 

 

 

 

 

 

 

 

~

(Undefined)

 

 

Unit No.

 

 

 

 

 

 

(Undefined)

 

 

Head CH No.

 

 

 

 

 

 

 

 

 

 

Leading address No.

 

(Undefined)

 

 

 

 

 

Read bytes

 

 

 

 

 

 

 

 

 

CH 1

CH N

* N: Number of Heads

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0006 to 0034

 

(4 digits BCD)

 

 

 

 

+1

Number of Heads

0001 to 0008

 

(4 digits BCD)

 

 

 

 

+(4(N–1)+2)

Unit No. (2 digits BCD)

Arbitrary (However, there is a limit for the

 

 

maximum Unit No. depending on the model)

 

 

 

+(4(N–1)+3)

R/W Head CH No.

R/W Head CH 1 designation: 1

 

(1 digit BCD)

R/W Head CH 2 designation: 2

 

 

 

 

The CD1D must be set to 1.

 

 

 

+(4(N–1)+4)

Leading address No.

0000 to FFFF

 

(4 digits Hexadecimal)

 

 

 

 

+(4(N–1)+5)

Read bytes

If number of Heads is 2 or less

 

(2 digits Hexadecimal)

01 to 76 (1 to 118 bytes)

 

 

 

 

 

If number of Heads is 4 or less

 

 

01 to 30 (1 to 48 bytes)

 

 

 

 

 

If number of Heads is 8 or less

 

 

01 to 20 (1 to 20 bytes)

N: Number of Heads

 

Receive Data Word Allocation (3rd Operand of PMCR)

None.

Note 1. Execute Sequence No. 510 before executing Sequence No. 511, 512, 513.

2.Execute Sequence No. 544 (Polling Auto-read Command Processing Cancel) to cancel the polling auto-read.

3.Retry processing is not performed for this sequence.

383

Page 386
Image 386
Omron CQM1H-SCB41 operation manual Auto-read Hexadecimal/1 Sequence No, Polling Auto-read Ascii Sequence No