Model number

Changes required for CQM1H-series product

products

 

 

 

 

 

Wiring

Other

 

 

 

 

 

 

C-series CPU

SRM1

No changes have been

It may be possible to use the host computer

Units

CPM1

made in wiring.

programs without alteration as long as the

 

 

same communications settings (e.g., baud

 

CPM1A

 

 

 

rate) are used. It may be necessary, however,

 

CPM2A/CPM2C

 

to change programs to allow for different

 

 

CQM1H command specifications.

 

CQM1-CPUjj-E

 

 

 

 

 

 

C200HS-CPUjj-E

 

 

 

 

C200HX/HG/HE-

 

 

 

 

CPUjj-E

 

 

 

 

C200HW-COMjj-E

 

 

 

 

 

 

 

CS1-series CPU

CS1G/H-CPUjj

No changes have been

It may be possible to use the host computer

Unit

 

made in wiring.

programs without alteration as long as the

 

 

 

same communications settings (e.g., baud

CS1-series

CS1W-SCB21/41

No changes have been

rate) are used. It may be necessary, however,

Serial

CS1W-SCU21

made in wiring.

to change programs to allow for different

Communications

 

 

 

 

CQM1H command specifications.

Board or Unit

 

 

 

 

 

 

 

 

 

 

CVM1 or

CVM1/CV-CPUjj

No changes have been

It may be possible to use the host computer

CV-series CPU

 

made in wiring.

programs without alteration as long as the

Units

 

 

same communications settings (e.g., baud

 

 

 

rate) are used. It may be necessary, however,

 

 

 

to change programs to allow for different

 

 

 

CQM1H command specifications.

 

 

 

 

CVM1 or

CV500-LK201

Port 1:

The following changes are necessary for

CV-series Host

 

The connector has been

half-duplex transmissions that use CD.

Link Unit

 

changed from a 25-pin to a

Check the system for timing problems when

 

 

9-pin connector.

 

 

using SEND(90), RECV(98), or CMND(––) to

 

 

 

 

 

Port 2 set for RS-232C:

initiate communications from the PC or timing

 

 

The SG signal has been

problems in sending commands from the host

 

 

changed from pin 7 to pin 9.

computer. If necessary, switch to full-duplex

 

 

 

transmissions.

 

 

 

The following changes are necessary for

 

 

 

full-duplex transmissions that do not use

 

 

 

CD.

 

 

 

Half-duplex It may be possible to use the host

 

 

 

computer programs without alteration as long

 

 

 

as the same communications settings (e.g.,

 

 

 

baud rate) are used. It may be necessary,

 

 

 

however, to change programs to allow for

 

 

 

different CQM1H command specifications.

Note The number of words that can be read and written per frame (i.e., the text lengths) when using C-mode Host Link commands is different for C-series Host Link Units and CQM1H-series Serial Communications Boards. A host computer program previously used for C-series Host Link Units may not function correctly if used for CQM1H-series PCs. Check the host computer program before using it and make any corrections required to handle different frame text lengths.

54

Page 66
Image 66