E5ZE Temperature Controller Read Protocol

Appendix E

 

 

 

Read Alarm Temperatures (Sequence No. 108)

Reads the alarm temperatures and stores the results in the specified words.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

Offset

Contents (data format)

 

Data

 

 

 

 

+0

Number of send data words

0002

(fixed)

 

(4 digits BCD)

 

 

 

 

 

 

+1

Unit No. (2 digits Hex)

00 to

0F

Receive Data Word Allocation (3rd Operand of PMCR)

Receive data

+0

 

Number of receive data words

 

 

 

storage words

 

 

 

 

 

 

+1

 

Alarm 1 set value (rightmost 4 digits)

 

 

 

 

 

 

 

 

 

 

 

 

+2

 

Alarm 1 set value (leftmost 1 digit)

 

 

 

 

 

 

 

 

 

+3

 

Alarm 2 set value (rightmost 4 digits)

 

 

 

 

 

 

 

+4

 

Alarm 2 set value (leftmost 1 digit)

 

 

 

 

 

 

 

 

 

 

 

~

~

 

 

 

 

 

 

 

 

+29

 

Alarm 1 set value (rightmost 4 digits)

 

 

 

 

+30

 

Alarm 1 set value (rightmost 1 digit)

 

 

+31

 

Alarm 2 set value (rightmost 4 digits)

 

 

+32

 

Alarm 2 set value (leftmost 1 digit)

 

 

 

 

 

 

 

Channel 0

Channel 7

Offset

Contents (data format)

Data

 

 

 

+0

Number of receive data words

0033

 

(4 digits BCD)

 

 

 

 

+1

Channel 0

0000 to 9999

 

Alarm 1 set value (rightmost 4 digits)

F indicates a negative number.

 

(4 digits BCD)

 

 

 

 

+2

Channel 0

0000 to 0009

 

Alarm 1 set value (leftmost 1 digit)

F indicates a negative number.

 

(4 digits BCD)

 

 

 

 

+3

Channel 0

0000 to 9999

 

Alarm 2 set value (rightmost 4 digits)

F indicates a negative number.

 

(4 digits BCD)

 

 

 

 

+4

Channel 0

0000 to 0009

 

Alarm 2 set value (leftmost 1 digit)

F indicates a negative number.

 

(4 digits BCD)

 

 

 

 

 

D

 

 

D

 

 

D

 

 

 

 

+29

Channel 7

0000 to 9999

 

Alarm 1 set value (rightmost 4 digits)

F indicates a negative number.

 

(4 digits BCD)

 

 

 

 

+30

Channel 7

0000 to 0009

 

Alarm 1 set value (leftmost 1 digit)

F indicates a negative number.

 

(4 digits BCD)

 

 

 

 

+31

Channel 7

0000 to 9999

 

Alarm 2 set value (rightmost 4 digits)

F indicates a negative number.

 

(4 digits BCD)

 

 

 

 

+32

Channel 07

0000 to 0009

 

Alarm 2 set value (leftmost 1 digit)

F indicates a negative number.

 

(4 digits BCD)

 

 

 

 

198

Page 204
Image 204
Omron CQM1H-SCB41 operation manual Read Alarm Temperatures Sequence No