Basic Operating Procedure

Section 1-2

1-1-5 Mounting Location

The Serial Communications Board can be installed in Inner Board slot 1 of a

CQM1H-series CPU Unit. The Board cannot be installed in slot 2.

Mount here

Not mountable

Slot 1:

Slot 2:

Serial Communications Board

1-2 Protocol Overview

The following six serial communications modes can be used as required for each serial communications port on the Serial Communications Board.

Host Link:

For connections to host computers, personal computer peripheral devices, or Programmable Terminals

Protocol Macros:

For communications with general-purpose external devices using protocols

No-protocol:

For connections to general-purpose devices for no-protocol communications using TXD(––) and RXD(––) instructions

1:1 Data Links:

For 1:1 data links with a C-series PC, including another CQM1H

1:N-mode NT Link:

For communications with one or more Programmable Terminals (PTs)

1:1-mode NT Link:

For communications with one PT

Communications Ports and Serial Communications Modes

Board

Port

 

 

Serial communications mode

 

 

 

 

 

 

 

 

 

 

 

 

 

Peripheral

Host Link

Protocol

No-

1:1 Data

1:N-mode

1:1-mode

 

 

bus or

(SYSMAC

macro

protocol

Link

NT Link

NT Link

 

 

Programming

WAY)

 

 

 

 

 

 

 

Console bus

 

 

 

 

 

 

Serial

RS-232C

No

OK

OK

OK

OK

OK (See

OK (See

Commu-

(port 1)

 

 

 

 

 

note 2)

note 2)

nications

 

 

 

 

 

 

 

 

RS-422A/

No

OK (See

OK

OK (See

OK (See

OK (See

OK (See

Boards

485 (port 2)

 

note 1)

 

note 1)

note 1)

note 2)

note 2)

 

 

 

 

 

 

 

 

 

 

 

 

Note 1. A 4-wire connection must be used when using Host Link, no-protocol, or 1:1 Data Link communications with an RS-422A/485 connector.

2. The PT Programming Control functions are not supported.

Connection examples for the serial communications modes are shown in the fol- lowing sections.