K3Tj Intelligent Signal Processor Protocol

 

 

Appendix I

 

 

 

 

 

 

 

 

 

 

 

Offset

Contents (data format)

 

 

Data

 

 

 

 

 

 

 

+0

Number of receive data

0006 to 0126

 

 

 

 

words (4 digits BCD)

 

 

 

 

 

 

 

 

 

 

 

 

 

+1 to

Input specifications (ASCII

544131

(“TA1”) (K3TH)

 

 

+ 2

3 characters)

544231

(“TB1”) (K3TH)

 

 

 

 

 

564432

(“VD2”) (K3TX)

 

 

 

 

 

414432

(“AD2”) (K3TX)

 

 

 

 

 

564132

(“VA2”) (K3TX)

 

 

 

 

 

414132

(“AA2”) (K3TX)

 

 

 

 

 

524231

(“RB1”) (K3TR, K3TC)

 

 

 

 

 

 

 

+2

Display specifications

41 (“A”) (common)

 

 

 

 

(ASCII 1 character)

42 (“B”) (K3TH, K3TX)

 

 

 

 

 

43 (“C”) (K3TR, K3TC)

 

 

 

 

 

 

 

 

+3

Output specifications (ASCII

5331

(“S1”) (RS-232C)

 

 

 

 

2 characters)

5332

(“S2”) (RS-485)

 

 

 

 

 

5333

(“S3”) (RS-422A)

 

 

 

 

 

5335

(“S5”) (RS-485 + comparison output)

 

 

 

 

 

5336

(“S6”) (RS-422A + comparison output)

 

 

 

 

 

 

 

+4

Input contents

Leftmost digit: 30 (“0”) to 31 (“1”)

 

 

 

 

(ASCII 2 characters)

 

 

 

 

 

 

 

Rightmost digit: 31 (“1”) to 45 (“E”)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+5

Operation mode

3030

(“00”) (K3TH, K3TX)

 

 

 

 

(ASCII 2 characters)

3031

(“00”) to 3133 (“12”) (K3TR)

 

 

 

 

 

5542

(“UB”) (K3TC)

 

 

 

 

 

5543

(“UC”) (K3TC)

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

+125

Operation mode

Same as above

 

 

 

 

(ASCII 2 characters)

 

 

 

 

 

 

 

 

 

 

 

 

Model Data Read (Continuous Units) (Sequence No. 338)

This sequence reads model data for continuous units.

Send Data Word Allocation (2nd Operand of PMCR)

First word of +0

send data

+1

Number of send data words

(Undefined)

Number of units

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0002

 

(4 digits BCD)

 

 

 

 

+1

Number of units

01 to 25

 

(2 digits BCD)

 

 

 

 

Note The number of Units can be up to 25 maximum.

Receive Data Word Allocation (3rd Operand of PMCR)

The work allocation is similar to sequence No. 337 (Model Data Read (by Unit Number)).

302

Page 307
Image 307
Omron CQM1H-SCB41 operation manual Model Data Read Continuous Units Sequence No