E5jK Digital Controller Write Protocol

Appendix D

 

 

 

Receive Data Word Allocation (3rd Operand of PMCR)

None.

Write Cooling Coefficient (Sequence No. 053)

Writes the cooling coefficient.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

 

+2

Cooling coefficient

 

 

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0003 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits BCD)

00 to 31

 

 

 

+2

Cooling coefficient (4 digits BCD)

0001 to 9999

Receive Data Word Allocation (3rd Operand of PMCR)

None.

Write Dead Band (Sequence No. 054)

Writes the dead band.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

 

+1

(Undefined)

 

Unit No.

 

 

 

 

 

 

 

 

+2

Dead band

 

 

 

 

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0003 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits BCD)

00 to 31

 

 

 

+2

Dead band (4 digits BCD)

0000 to 9999

Receive Data Word Allocation (3rd Operand of PMCR)

None.

Write Manual Reset Value (Sequence No. 055)

Writes the manual reset value.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

 

+2

Manual reset value

 

 

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0003 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits BCD)

00 to 31

 

 

 

+2

Manual reset value (4 digits BCD)

0000 to 1000

Receive Data Word Allocation (3rd Operand of PMCR)

None.

Write Hysteresis (Sequence No. 056)

Writes the hysteresis for heating and for cooling.

173

Page 180
Image 180
Omron CQM1H-SCB41 Write Cooling Coefficient Sequence No, Write Dead Band Sequence No, Write Manual Reset Value Sequence No