ConnectionsSection 4-4

4-4-4

End Codes

 

 

 

The response (end) codes listed in the following table are returned in the re-

 

sponse frame for Host Link commands. When two or more errors occur, the end

 

code for the first error will be returned.

 

 

 

 

 

End

Contents

Probable cause

Corrective measures

code

 

 

 

00

Normal completion

No problem exists.

---

 

 

 

 

01

Not executable in RUN

The command that was sent cannot be

Check the relation between the

 

mode

executed when the PC is in RUN mode.

command and the PC mode.

02

Not executable in MON-

The command that was sent cannot be

 

 

ITOR mode

executed when the PC is in MONITOR

 

 

 

mode.

 

 

 

 

 

03

UM write-protected

The PC’s UM is write-protected.

Turn OFF pin 1 of the CPU Unit’s

 

 

 

DIP switch (SW1).

04

Address over

The program address setting in an read or

Check the program.

 

 

write command is above the highest program

 

 

 

address.

 

 

 

 

 

13

FCS error

The FCS is wrong.

Check the FCS calculation meth-

 

 

 

od. If there was influence from

 

 

 

noise, transfer the command

 

 

 

again.

14

Format error

The command format is wrong, or a com-

Check the format and transfer the

 

 

mand that cannot be divided has been di-

command again.

 

 

vided, or the frame length is smaller than the

 

 

 

minimum length for the applicable command.

 

 

 

 

 

15

Entry number data error

The data is outside of the specified range or

Correct the data and transfer the

 

 

too long.

command again.

 

 

Hexadecimal data has not been specified.

 

 

 

 

 

16

Command not supported

The operand specified in an SV Read or SV

Check search data or the search

 

 

Change command does not exist in the pro-

starting point.

 

 

gram.

 

 

 

 

 

18

Frame length error

The maximum frame length of 132 bytes was

Check the command and divide it

 

 

exceeded.

into multiple frames if necessary.

 

 

If the frame exceeds 280 bytes, the Recep-

 

 

 

tion Overflow Flag will be turned ON and

 

 

 

there will not be a response.

 

 

 

 

 

19

Not executable

The read SV exceeded 9,999, or an I/O

Register items to read before at-

 

 

memory batch read was executed when

tempting batch read.

 

 

items to read were not registered for com-

 

 

 

pound command.

 

 

 

 

 

23

User memory protected

The UM is write-protected.

Turn OFF the write-protection

 

 

 

 

A3

Aborted due to FCS error in

An FCS error occurred in the second or later

Correct the command data and

 

transmission data

frame, or there were two bytes or less of

transfer the command again.

 

 

data in an intermediate or final frame for mul-

 

 

 

tiple writing.

 

 

 

 

 

A4

Aborted due to format error

The command format did not match the

 

 

in transmission data

number of bytes in the second or later frame.

 

A5

Aborted due to entry num-

There was an entry number data error in the

 

 

ber data error in transmis-

second or later frame, a data length error, or

 

 

sion data

data was not set in hexadecimal.

 

 

 

 

 

A8

Aborted due to frame length

The length of the second and later frames

 

 

error in transmission data

exceeded the maximum of 128 bytes.

 

52

Page 64
Image 64
Omron CQM1H-SCB41 operation manual End Codes, End Contents Probable cause Corrective measures Code