Application Procedure

Section 4-2

shown below. Perform other processing as required, such as setting switches on the external device(s).

Serial Communications Board

RS-232C

RS-422A3G2A9-AL001

RS-232C /485

RS-422A /485

NT-AL001-E Terminating resistance ON, 5-V power supply required

Terminating resistance

ON

The CPU Unit can be connected to a Programming Console, the CX-Pro- grammer, or the CX-Protocol as required.

4.Turn ON power.

5.Set the PC Setup settings for the Serial Communications Board.

Use a Programming Console, the CX-Programmer, or the CX-Protocol to set the settings in the PC Setup between DM 6550 and DM 6559.

Note The settings stored in these words are read constantly; the PC does not need to be restarted or reset when changes are made to the set- tings. They will be updated automatically as soon as they are changed.

The following table shows the standard settings.

Port 1

Port 2

Bit(s)

Default

Function

 

 

 

setting

 

 

 

 

 

 

DM 6555

DM 6550

00 to 03

0 Hex

Standard port settings

 

 

 

 

(1 start bit, 7-bit data, even par-

 

 

 

 

ity, 2 stop bits, 9,600 bps)

 

 

 

 

 

 

 

04 to 07

0 Hex

CTS control disabled

 

 

 

 

 

 

 

08 to 11

---

Not used.

 

 

 

 

 

 

 

12 to 15

0 Hex

Communications mode

 

 

 

 

0: Host Link

 

 

 

 

 

DM 6556

DM 6551

00 to 07

---

Baud rate: invalid

 

 

 

 

 

 

 

08 to 15

---

Frame format: Invalid

 

 

 

 

 

DM 6557

DM 6552

00 to 15

0000 Hex

Transmission delay: 0 ms

 

 

 

 

 

DM 6558

DM 6553

00 to 07

00 BCD

Node number 00

 

 

 

 

 

 

 

08 to 11

---

Not used.

 

 

 

 

 

 

 

12 to 15

---

Not used.

37

Page 49
Image 49
Omron CQM1H-SCB41 operation manual Port Bits Default Function Setting