Appendix FE5ZE Temperature Controller Write Protocol
220
Write Ramp Value (Sequence No. 164)

Writes the ramp values.

Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data Number of send data words+0
+1
+2
+3
+4
+5
+16
+17
(Undefined) Unit No.
Ramp value
(Undefined)
~ ~
Channel 0
Channel 7
Channel 1
Ramp value
Time unit (Undefined)
(Undefined) Ramp value
Time unit (Undefined)
(Undefined)
Time unit (Undefined)
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD) 0018 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
+2 Channel 0
Ramp value (3 digits BCD) 000 to 999
+3 Channel 0
Time unit (one ASCII character) S: Seconds; M: Minutes; H: Hours
+4 Channel 1
Ramp value (3 digits BCD) 000 to 999
+5 Channel 1
Time unit (one ASCII character) S: Second M: Minute H: Hour
+16 Channel 7
Ramp value (3 digits BCD) 000 to 999
+17 Channel 7
Time unit (one ASCII character) S: Seconds; M: Minutes; H: Hours
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Manual Output Value (Sequence No. 165)

Writes the manual output values for control output in manual operation.

Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data Number of send data words+0
+1
+2
+3
+4
+5
+16
+17
(Undefined) Unit No.
Output value
~ ~
Cooling output value
Output value
Cooling output value
Channel 0
Channel 7
Output value
Cooling output value Channel 1