Image 24

Installation

Section 2-1

!Caution Do not connect the 5-V power supply of pin 6 to any external device other than an NT-AL001-E Link Adapter. Otherwise, the external device and the Serial Com- munications Board may be damaged.

The following cables are provided for connection to NT-AL001-E Link Adapters.

We recommend that these cables be used.

NT-AL001-E connecting cables: XW2Z-070T-1 (0.7 m)

 

XW2Z-200T-1 (2 m)

Applicable Connectors

Socket: XM2A-0901 (OMRON) or equivalent

 

Hood: XM2S-0911-E (OMRON, conforms to ESD) or equivalent

 

One Socket and one Hood are provided for each port.

Recommended Cables

UL2464 AWG28 5P IFS-RVV-SB (UL-approved, Fujikura Ltd.)

 

AWG28 5P IFVV-SB (not UL-approved, Fujikura Ltd.)

 

UL2464-SB (MA) 5P 28AWG (7/0.127) (UL-approved, Hitachi Cable, Ltd.)

 

CO-MA-VV-SB 5P 28AWG (7/0.127) (not UL-approved, Hitachi Cable, Ltd.)

 

Cable length: 15 m max.

2-1-3 RS-422A/485 Port

Protocol

Host Link

No-protocol

Protocol macros

1:1 Data Links

1:N NT Links

1:1 NT Links

 

 

 

 

 

 

 

Communica-

Half-duplex

 

 

 

 

 

tions method

 

 

 

 

 

 

4-wire, 1:1

OK

OK

OK

OK

OK

OK

 

 

 

 

 

 

 

4-wire, 1:N

OK

OK

OK

No

OK

No

 

 

 

 

 

 

 

2-wire, 1:1

No

No

OK

No

OK

No

 

 

 

 

 

 

 

2-wire, 1:N

No

No

OK

No

OK

No

 

 

 

 

 

 

 

Synchroniza-

Start-stop synchronous (asynchronous)

 

 

 

tion

 

 

 

 

 

 

Baud rate

1,200/2,400/4,800/9,600/ 19,200 bps

19,200 bps

38,400 bps

19,200 bps

 

 

 

 

 

 

Connections

1:N (N: 32 Units max.)

 

1:1

1:N (N: 8 Units

1:1

 

 

 

 

 

max.)

 

 

 

 

 

 

 

 

Transmission

500 m max.

 

 

 

 

 

distance

(The total combined cable length is 500 m max. T-branch lines must be a maximum of 10 m long.)

 

 

 

 

 

 

Interface

Complies with EIA RS-485

 

 

 

 

Connector Pin Layout

Pin No.

Abbreviation

Signal name

I/O

 

 

 

 

1 (See note 1)

SDA

Send data –

Output

 

 

 

 

2 (See note 1)

SDB

Send data +

Output

 

 

 

 

3

NC

Not used

---

 

 

 

 

4

NC

Not used

---

 

 

 

 

5

NC

Not used

---

 

 

 

 

6 (See note 1)

RDA

Receive data –

Input

 

 

 

 

7

NC

Not used

---

 

 

 

 

8 (See note 1)

RDB

Receive data +

Input

 

 

 

 

9

NC

Not used

---

 

 

 

 

Shell (See note 2)

FG

Shield

---

Note 1. When 2-wire connections are used, use pins 1 and 2, or pins 6 and 8.

2.The shell is connected to the ground terminal (GR) of the Power Supply Unit inside of the Serial Communications Board. Therefore, the cable shield can be grounded by grounding the GR of the Power Supply Unit.