Board Replacement

 

 

 

Section 9-2

 

Serial Communications

For Serial Communications Boards, refer to the following error flags. When an

Board Error Information

error occurs, the corresponding flag is turned ON. All of these flags represent

 

 

 

 

non-fatal errors.

 

 

 

 

 

 

 

 

 

 

 

 

 

Word

Bit

 

Name

 

Probable cause

Possible remedy

 

 

 

 

 

 

 

 

IR 200

00

Serial Communications Board

The Board has failed.

Secure the Board firmly in the

 

 

 

Hardware Error Flag

 

 

slot or try it in a different CPU

 

 

 

 

 

 

 

Unit. If the problem persists,

 

 

 

 

 

 

 

replace the Board.

 

 

01

Port Identification Error Flag

There is a problem with the

Replace the Board.

 

 

 

(hardware error)

communications port.

 

 

 

 

02

Protocol Data Error Flag

A checksum error was found in

Retransfer the protocol data.

 

 

 

 

 

the protocol data.

If the problem persists,

 

 

 

 

 

 

 

replace the Board.

 

 

 

 

 

 

 

 

 

12/11

Protocol Macro Execution

An error occurred when the

Take countermeasures

 

 

 

Error Flag (Port 1/2)

PMCR instruction was executed.

according to the error codes

 

 

 

 

 

 

 

stored in bits 08 to 11 (port 1)

 

 

 

 

 

 

 

or bits 12 to 15 (port 2) in

 

 

 

 

 

 

 

word 204.

 

 

 

 

 

 

 

 

 

15

PC Setup Error Flag

There is an error in the settings in

Check the settings for the

 

 

 

 

 

the PC Setup.

Board in the PC Setup and

 

 

 

 

 

 

 

restart the Board.

 

 

14

Port 1 PC Setup Error Flag

 

Error in settings for port12.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

Port 2 PC Setup Error Flag

 

Error in settings for port 2.

 

 

 

 

 

 

 

 

 

 

SR 254

15

Slot 1 Inner Board Error Flag

Turns ON when an error occurs

See remedies for AR 04.

 

 

 

 

 

in the slot 1 Inner Board. The

 

 

 

 

 

 

 

error code for slot 1 is stored in

 

 

 

 

 

 

 

AR 0400 to AR 0407.

 

 

 

 

 

 

 

 

 

 

 

AR 04

00 to 07

Slot 1 Inner Board Error Code

 

 

 

 

 

 

 

 

 

 

 

 

 

01: Hardware error

The Board has failed (watchdog

Secure the Board firmly in the

 

 

 

 

 

timer error). IR 20000 will also be

slot or try it in a different CPU

 

 

 

 

 

ON.

Unit. If the problem persists,

 

 

 

 

 

 

 

replace the Board.

 

 

 

02: Hardware error

The Board has failed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10: Serial Communications

Refer to the errors in IR 200.

See remedies for IR 20000,

 

 

 

Board error

 

 

 

IR 20001, IR 20002, IR

 

 

 

 

 

 

 

20011, IR20012, and

 

 

 

 

 

 

 

IR 20015.

When a fatal error occurs, the ERR/ALM indicator on the CPU Unit will light.

When a non-fatal error occurs, the ERR/ALM indicator on the CPU Unit will flash.

Refer to the indicator error displays.

Note The ERR/ALM indicator will continue to flash even after the cause of a non-fatal error has been removed for the Serial Communications Board. The indicator can be stopped by clearing the error from a Programming Console or other Program- ming Device. Press the FUN Key and then the MONITOR Key from the Pro- gramming Console. Refer to the CX-Programmer Operation Manual for the CX- Programmer procedure.

9-2

Troubleshooting

 

 

 

 

 

 

This section describes how to resolve transmission and reception problems.

9-2-1

Host Link Communications

 

 

 

 

 

 

 

 

Serial com-

Indicator

Status

I/O memory

Cause

Remedy

munications

status

information,

 

 

 

mode

 

etc.

 

 

 

121

Page 129
Image 129
Omron CQM1H-SCB41 operation manual Troubleshooting, Serial Communications, Board Error Information