E5jK Digital Controller Read Protocol

Appendix C

 

 

 

 

 

 

 

 

 

Offset

Contents (data format)

Data

 

 

 

 

 

 

 

+0

Number of receive data words

Number of units  8 + 1

 

 

 

 

(4 digits BCD)

 

 

 

 

 

 

 

 

+1

1st unit

0000: s, 0001: hr

 

 

 

 

SP ramp time unit (4 digits BCD)

 

 

 

 

 

 

 

 

+2

1st unit

0000 to 9999

 

 

 

 

SP ramp set value (4 digits BCD)

 

 

 

 

 

 

 

 

+3

1st unit

0000 to 9999

 

 

 

 

LBA detection time (4 digits BCD)}

 

 

 

 

 

 

 

 

+4

1st unit

F050 to 1050

 

 

 

 

MV at stop (4 digits BCD)

F indicates a negative value.

 

 

 

 

 

A050 to 1050 for heating/cooling control

 

 

 

 

 

A indicates a negative value.

 

 

 

 

 

 

 

+5

1st unit

F050 to 1050

 

 

 

 

MV at PV error (4 digits BCD)

F indicates a negative value.

 

 

 

 

 

A050 to 1050 for heating/cooling control

 

 

 

 

 

A indicates a negative value.

 

 

 

 

 

 

 

+6

1st unit

MV lower limit + 1 to 1050

 

 

 

 

MV upper limit (4 digits BCD)

0000 to 1050 for heating/cooling control

 

 

 

 

 

 

 

+7

1st unit

F050 to MV upper limit –1

 

 

 

 

MV lower limit (4 digits BCD)

F indicates a negative value.

 

 

 

 

 

A050 to 1050 for heating/cooling control

 

 

 

 

 

A indicates a negative value.

 

 

 

 

 

 

 

 

+8

1st unit

0000 to 1000

 

 

 

 

MV change rate limit

 

 

 

 

 

(4 digits BCD)

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

D

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

+64

8th unit

0000 to 1000

 

 

 

(max.)

MV change rate limit

 

 

 

 

 

(4 digits BCD)

 

 

 

 

 

 

 

 

Read Level 2 Parameters 2 (Sequence No. 022)

Reads parameters in level 2 (input digital filter, alarm 1 hysteresis, alarm 2 hysteresis, alarm 3 hysteresis, input shift upper limit, and input shift lower limit) from multiple units and stores the results in the specified words.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

 

Number of send data words

 

send data

 

 

 

 

 

+1

 

Number of units

 

 

 

 

 

 

 

 

 

 

 

+2

 

(Undefined)

Unit No.

 

 

 

 

 

 

 

 

 

 

 

+3

 

(Undefined)

Unit No.

 

 

 

 

 

 

 

 

~

 

~

+9

(Undefined)

Unit No.

(max.)

Offset

Contents (data format)

Data

+0

Number of send data words

Number of units + 2

 

(4 digits BCD)

 

+1

Number of units (4 digits BCD)

0001 to 0008

+2 to 9 Unit No. (2 digits BCD)

00 to 31

168

Page 175
Image 175
Omron CQM1H-SCB41 operation manual Read Level 2 Parameters 2 Sequence No, Appendix C