Appendix H
ES100j Digital Controller Protocol
252
Offset Contents (data format) Data
+0 Number of receive data words
(4digits BCD) Number of units 2 + 1
+1 1st unit
PV data (rightmost 4 digits)
(4 digits BCD)
00000000 to 09999000
F indicates a negative number.
+2 1st unit
PV data (leftmost 4 digits)
(4 digits BCD)
+3 2nd unit
PV data (rightmost 4 digits)
(4 digits BCD)
00000000 to 09999000
F indicates a negative number.
+4 2nd unit
PV data (leftmost 4 digits)
(4 digits BCD)
+63 32nd unit
PV data (rightmost 4 digits)
(4 digits BCD)
00000000 to 09999000
F indicates a negative number.
+64 32nd unit
PV data (leftmost 4 digits)
(4 digits BCD)
Read SP Data (Sequence No. 255)

Reads the SP data for the variable type analog data in the variable area.

Send Data Word Allocation (2nd Operand of PMCR)
(Undefined) Unit No.
First word of
send data Number of send data words+0
+1
+2
+3
+33
(Undefined) Unit No.
Number of units
(Undefined) Unit No.
~ ~32nd unit (max.)
2nd unit
1st unit
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD) Number of units + 2
+1 Number of units (4 digits BCD) 0001 to 0032
+2 1st unit
Unit No. (2 digits BCD) 00 to 31
+3 2nd unit
Unit No. (2 digits BCD) 00 to 31
+33
(max.) 32nd unit
Unit No. (2 digits BCD) 00 to 31